HarshIO 300 ePN
40
IP67 Digital I/O Modules for PROFINET IO
To perform the reset, power on the module with the rotary switches in
position 900, wait 5 sec and power off the module. The module is now
configured with the following parameters:
Module factory settings:
PROFINET name
molex-harsh300-ip67
Rotary switch Position
700
IP address:
0.0.0.0
Subnet mask:
0.0.0.0
Gateway:
0.0.0.0
ETH1 port:
Auto negotiation / Auto MDIX
ETH2 port:
Auto negotiation / Auto MDIX
LLDP:
Enabled
Easy Replacement:
Enabled
999
Reserved for technical support (firmware download)
Note: The rotary switch position is ONLY read at the boot of the module. Any modification of the position will
require a power cycle (ON
OFF
ON) of the module.
Note: All other rotary switch positions are forbidden. In all of these cases, the HarshIO module will not start
and the MOD led status will blink in RED.
Note: If a DCP request is received, and the rotary switches are not on DCP mode (position 700), the module
will reject the request.