Assigning device name
Before assigning a device name, you have to identify the HarshIO module on the PROFINET network. The
identification of a PROFINET device is performed using the MAC address and the device type.
Remember, the HarshIO module must be physically connected to the Siemens controller to able the
identification.
Select
PLC
menu
Ethernet
Edit Ethernet Node
and click on Browse to open the
Browse Network
dialog
box. Click Start to start the discovery.
Fig. G: List of detected PROFINET devices
The identification of a HarshIO module is done using a blink test command. This test causes the Module
status LED to BLINK continuously.
To perform the identification test, choose a HarshIO module in the detected device list and click
Flash
button.
Remember! HarshIO module has the following default factory settings
MAC address: 00-A0-91-xx-xx-xx
IP address:
0.0.0.0