4 Installation
4.4 Installing
XP-503 01/2017 MN048014 EN www.eaton.com
25
4.4.6
Conditions for marine approval
The following DNV GL rules for shipping classification in accordance with DNV GL-CG-0339 type
approvals must be observed:
1
Complete and proper installation and commissioning in accordance with DNV GL rules and
Eaton requirements and specifications.
2
Installation of radio interference suppression filters for the 24-V-DC-supply.
Radio interference suppression filter for the 24-V-DC-supply
Additional interference filters must be installed for the power supply in order to adhere to the EMC B
provisions.
Integrate a radio interference suppression filter into the wiring.
Depending on the output, the following filters can be used:
•
XT-FIL-1 radio interference suppression filter for 24-V-DC supply up to 2.2 A (Eaton article no.
285316) or
•
XT-FIL-2 radio interference suppression filter for 24-V-DC supply up to 12 A (Eaton article no.
118980)
Abb. 6
Power supply with EMC filter
Grounding is ensured either by using
the filter's integrated contact fields onto a grounded metal plate
or using
a separate line to the filer's PE connection.
Depending on the current consumption or configuration, several filters may be used as well.