Device Description MC-HPG-2x0
Display PLC
MC-HPG-2x0
Mounting instructions
7 M
OUNTING INSTRUCTIONS
7.1 G
ENERAL MOUNTING INSTRUCTIONS
All MC-HPG-2x0 series devices are mounted from the front, i.e. in a control
panel. They are fastened from the rear with the supplied fixing frame and 4
securing nuts.
All MC-HPG-2x0 series devices can be operated up to a maximum ambient
temperature of 45°C (
Section12 ). The ambient temperature stated
applies to the area in the direct vicinity of the lower connectors, if the device
is mounted vertically with unimpeded air convection and a maximum
operating height of 2000m above sea level. The cooling slots must always
be free in order to ensure the proper cooling of the system.
The device can be mounted in an enclosure if the ambient temperature is
taken into consideration. Provide a wall clearance of at least 50 mm on all
sides of the housing, so that sufficient air circulation is ensured. A minimum
clearance of 75 mm from active elements such as load current supply,
transformers etc. must be ensured.
Avoid the exposure of the flat screen to direct sunlight. The radiation from
the sun (UV component) reduces the lifespan of the LCD display.
The following must be ensured in order to prevent the
device from overheating during operation:
-
The cooling slots must always be free in order to
ensure the proper cooling of the system.
-
Avoid the exposure of the flat screen to direct
sunlight.
-
The mounting angle must not exceed ± 35° from
the vertical
If these conditions cannot be met, the mounting of an
external fan is recommended ( Section 7.5)
7.2 M
OUNTING IN THE FRONT PANEL
1. Push the MC-HPG-2x0 from the front into the cutout ( Section 7.3) of
the front panel.
2. The front seal must be level and evenly positioned between the front
plate and the front panel.
3. Centering the device in the cutout
4. Secure the device from the rear with the supplied fixing frame. For this
use the 4 securing nuts which should be tightened evenly from the rear
until the front frame is flush with the front panel all round.
Ensure that the seal is fitted correctly on the front panel.
Avoid tightening torques of greater than 0.3 Nm as this
could otherwise damage the device.
The thickness of the front plate must not exceed 5 mm.
04/05 AWB2776-1574GB
©
by Moeller GmbH
31
Summary of Contents for MC-HPG-2x0 Series
Page 4: ...II ...