Device Description MC-HPG-2x0
Display PLC
MC-HPG-2x0
Commissioning
bus terminating resistor
Station n
Station 1
Inside: twisted pair cable
Shield
Pin 3 and 6 (CAN_GND) are both connected internally with the CAN
Ground. Pins 4, 5 and 8 must
not
be connected! The CAN bus driver is fed
internally.
Baud rate and cable lengths
Baud rate
Max. length
20kBit/sec 2500m
25kBit/sec 2000m
50kBit/sec 1000m
100kBit/sec 650m
125kBit/sec 500m
250kBit/sec 250m
500kBit/sec 100m