MC-HPG-2x0
Display PLC
Device Description MC-HPG-2x0
Operation
6.3 PLC
OPERATING STATES
Power on
In Power on status, there is no user program in the PLC. In this status it is
possible to load a program onto the PLC. The Power on status is indicated
in the programming software.
Stop
The Stop operating status has the following features:
•
A user program is stored on the PLC
•
The user program is not running
The Stop status is selected:
•
After power on, if the entry Startup=STOP has been made in the
PLC.INI file (
Section 6.7)
•
After power on, if the entry Startup=AUTO has been made in the
PLC.INI file (
Section 6.7), and the PLC was in Stop status at the
last online access via the programming software
•
Via the programming software in the PC
•
After the cycle time is exceeded
Run
In RUN status, the user program is processed cyclically.
The RUN operating status is selected:
•
After power on, if the entry Startup=WARM has been made in the
PLC.INI file (
Section 6.7) (Default)
•
Via the programming software in the PC
•
After power on, if the entry Startup=AUTO has been made in the
PLC.INI file (
Section 6.7), and the PLC was in Run status at the
last online access via the programming software
System Fault SF
The following system faults can occur (
Section 10):
•
Hardware fault
•
Firmware system faults
04/05 AWB2776-1574GB
©
by Moeller GmbH
26