Programming the Control
Signal Terminals
01/02 AWB8230-1413GB
88
Heavy mains starting (CS)
The CS function is used for starting drives with an extremely high
starting torque directly from the mains. This means that a smaller,
less expensive frequency inverter can be used, since the DF6 has
to deliver only the motor full load current, not the high starting
current (for example 50 A starting current, 15 A motor full load
current).
To use this function, the system must be wired as shown in
figure 79.
Figure 79:
DF6 series frequency inverters with K2M bypass contactor, K3M motor contactor and K1M mains contactor
F11: 6 A miniature circuit-breaker, for example FAZ-B6
L1 L2 L3
L1
L2
L3
PE
K1M
K2M
Q1
L1
L2
L3
L3
L2
L1
5
3
1
5
3
1
L1
Z1
Z2
PE
PE
U
V
W PE
TH
CM1
M1
K3M
DF6-340-...
DV6-340-...
I
I
I
Q11
I
I
I
e
K11
F11
P24 FW
FWD
CS
2
PE
R0 T0
M 3
h
efesotomasyon.com - Klockner Moeller - inverter