Setting Parameters
01/02 AWB8230-1413GB
134
b005
Number of
restart
attempts
–
j
00
16 restart attempts at intermittent supply failure or
undervoltage.
00
01
The number of restart attempts is not limited.
b006
Mains phase
failure
detection
1)
–
j
00
Inactive
00
01
Active
b007
Synchronizatio
n frequency
–
j
0 to 400 Hz
When the frequency corresponding to the motor speed is
higher than the frequency programmed here, the frequency
inverter synchronizes itself with the motor speed and
accelerates to the setpoint value.
When the frequency corresponding to the motor speed is
lower than the frequency programmed here, the frequency
inverter starts at 0 Hz.
0.00
1) Phase failure detection can not be used if you are using the DF6 frequency
inverter with an RFI filter.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended