01/02 AWB8230-1413GB
Start/stop
71
.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
A001
Defined
frequency
setpoint
–
–
00
Definition with the potentiometer on the keypad
01
01
Definition through analog input O (0 to 10 V), OI
(4 to 20 mA) or O2 (–10 V to +10 V
H
)
02
Definition via PNU F001 and/or PNU A020
03
Definition through RS 485 serial interface, terminals: RP,
2
x
SN and SP
04
Definition via optional card at slot 1
05
Definition via optional card at slot 2
A019
Selection of
fixed frequency
actuation
–
–
00
Binary (FF1 to FF4)
00
01
Bitwise (SF1 to SF7)
A020
A220
Frequency
setpoint value
j
j
0 to PNU A004
You can enter a frequency setpoint value. You must set
PNU A001 to 02 for this purpose.
0.0
A021
Fixed
frequency
You can assign a frequency to each of the seven fixed
frequency parameters of PNU A021 to A027.
A022
A023
...
A027
F001
Input/display
frequency
value
Indication of the current frequency setpoint value or the
current fixed frequency.
To save modified values, press the ENTER key according to
the selection of the digital inputs configured as SF1 to SF7.
Resolution
g
0.1 Hz