Start/stop
77
Reset (RST)
A fault message can be acknowledged by activating and
subsequently deactivating (i.e. resetting) the digital input
configured as RST.
X
Program one of the digital inputs 1 to 5 as RST by entering the
value 18 under the corresponding PNU (C001 to C005).
By default, RS is assigned to digital input 1.
Under PNU C103, you can select how the frequency inverter
responds after the reset signal drops out. You can specify whether
the frequency inverter synchronizes to the frequency set under
PNU b007 or starts at 0 Hz.
Figure 67:
Digital input 4 configured as RST (reset)
RST
P24
4
Figure 68:
Function chart for RST (reset)
K14: Signalling relay contact K14
RST
f
12 ms
~ 30 ms
K14
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b003
Waiting time
before restart
–
j
0.3 to 100 s
Here, set a time which is to expire before an automatic
restart is initiated after a fault signal. This time can also be
used in conjunction with the FRS function. During the delay,
the following message appears on the LED display:
1.0
b007
Synchronizing
frequency
–
j
0 to 400 Hz
Frequency at which a restart is initiated.
0.0
C102
Reset signal
j
j
00
Reset signal issued on a rising edge
00
01
Reset signal issued on a falling edge
02
Reset signal issued on a rising edge, only if fault signal
present
C103
Behaviour on
reset
–
j
00
0 Hz start
00
01
Synchronization to the motor speed
Warning!
If a reset is carried out after a fault, the motor will start
immediately if a start signal is applied simultaneously. To
avoid the risk of serious or fatal injury to personnel, you
must ensure that the start signal is not present before
acknowledging an error message with a reset .
h
When a fault has occurred, the OFF key on the keypad
acts as a RESET key, and can be used instead of the RST
input to reset the fault.
h
If the RST input is active for more than four seconds, it can
cause a false trip.
h
The RST input is always a make (NO) contact and cannot
be programmed as a break (NC) contact.
h
Alternatively, you can acknowledge a fault message by
briefly switching the supply voltage off and on again.
h
If a reset is initiated during operation, the motor coasts to
a stop.