01/02 AWB8230-1413GB
Standard form for user defined
parameter settings
175
C022
Signal to relay output K33-K34 (values
a
PNU C021)
–
00
94
C026
Signal to relay terminals K11-K12
(values
a
PNU C021)
–
05
93
C027
Output, FM output
• 00: Output frequency, PWM signal
• 01: Output current
• 03: Output frequency, FM signal
• 04: Output voltage
• 05: Inverter input power
• 07: Ramp frequency
–
00
58
C028
Output, AM output
• 00: Output frequency, PWM signal
• 01: Output current
• 04: Output voltage
• 05: Inverter input power
• 06: Thermal load ratio
• 07: Ramp frequency
–
00
57
C029
Output, AMI output (values
a
PNU C028)
–
00
58
C031
Relay output K23-K24
• 00: Make contact
• 01: Break contact
–
00
94
C032
Relay output K33-K34 (values
a
PNU C031)
–
00
94
C036
Relay terminals K11K12, signalling relay
(values
a
PNU C031)
–
01
93
C040
Overload alarm signal
• 00: Always
• 01: Only at constant speed
–
01
97
C041
Threshold for overload alarm at digital relay output
K11 to K34
[A]
I
e
97
C042
Frequency from which FA2 is switched on during
acceleration
[Hz]
0.00
95
C043
Frequency from which FA2 is switched off during
deceleration
[Hz]
0.00
95
C044
PID control deviation
(from the maximum setpoint value)
[%]
3.0
98
PNU
Function
Units
WE
Page
Setpoint
efesotomasyon.com - Klockner Moeller - inverter