background image

5-571.4

12

12

start-uP ProceDure

gas control options

The unit must be reviewed to determine if any of the listed gas 

control options were supplied.

 time Delay relay

The Time Delay Relay is factory installed in the duct furnace 

electrical junction box. The standard duct furnace is provided 

for instantaneous fan operation. On a call for heat, the blower is 

energized at the same time as the gas controls. The optional time 

delay relay allows the gas controls to operate for approximately 30 

seconds before the blower starts. This allows the heat exchanger 

a warm up period so that the initial delivered air coming out of the 

ductwork is not cool. The time delay relay also keeps the motor 

running for approximately 30 seconds after the call for heat has 

been satisfied to remove the residual heat from the heat exchanger.

 low gas Pressure switch

The low gas pressure switch is factory installed in the duct furnace 

above the gas train. The switch monitors the gas pressure 

upstream of all the gas controls and shuts off the electric supply 

to the ignition controller and combination gas valve if low gas 

pressure is experienced. This will shut off all gas flow to the burner. 

The switch has an automatic reset so that if the gas pressure 

is interrupted and then is returned, the switch will automatically 

allow the unit to operate when gas conditions are returned to the 

allowable range of the pressure switch. The pressure switch range 

is 2" to 14" W.C. and should be set to insure that the minimum inlet 

gas pressure is available (6" W.C. for natural gas, 11" W.C. for 

propane gas). 

 High gas Pressure switch

The high gas pressure switch is factory installed in the duct 

furnace above the gas train. The switch monitors the gas pressure 

downstream of all the gas controls and shuts off the electric supply 

to the ignition controller and combination gas valve if high gas 

pressure is experienced right before the manifold. This will shut off

all gas flow to the burner. The switch has a manual reset so that if 

the gas pressure is too high, a service person must check the unit 

to make sure that none of the gas controls have been damaged 

by the high gas pressure and then reset the switch to allow the 

unit to operate when gas conditions are returned to the allowable 

range of the pressure switch. The pressure switch range is 2" to 16" 

W.C. and should be set to insure that the maximum manifold gas 

pressure is not exceeded (3.5" W.C. for natural gas, 10" W.C. for 

propane gas).

 supply air fire stat

The fire stat is factory installed in the duct furnace electrical junction 

box with the sensor in the discharge air stream. In case of elevated 

temperatures in the supply air, the manual reset switch shuts 

down the entire unit. If the limit temperature is exceeded, a service 

person must inspect the unit for the cause of the high discharge 

temperature, take corrective action, and then reset the switch.

 timed freeze Protection

The timed freeze protection system is factory installed in the duct 

furnace electrical junction box with the sensor (30°-75°F adjustable) 

factory installed in discharge air stream. On initial start-up, the 

timed delay in the system allows the unit to go through the normal 

ignition sequence. The timed delay is an automatic reset switch and 

adjustable for 1-10 minutes. In the event that the unit fails to fire 

after this period, the discharge air sensor will sense the cold air and 

will shut down the entire unit.

figure 12.1 - location of gas control options

 air flow Proving switch

The air flow proving switch is factory installed in the duct furnace 

electrical junction box. The air flow proving switch monitors the 

pressure differential between the duct furnace and the atmosphere. 

The purpose of the air flow proving switch is to cut power to the 

gas controls if a positive pressure is not measured by the switch. 

This could be caused by a lack of air movement through the heat 

exchanger.  
note:  The air flow proving switch will prevent any heat 

exchanger warm-up (the unit should not be equipped with 

a time delay relay) because the gas controls can not be 

energized until air flow is proven.

setting the air flow Proving switch

The range of the air flow proving switch is adjustable between 0.17" 

to 5.0" W.C.
1.  Set the thermostat so that there is a call for heat. This should 

start the blower and then the burner ignition sequence.

2.  Turn the set screw of the pressure switch clockwise until it 

stops. This will set the pressure at 5.0" W.C.

3.  Turn the screw counter-clockwise until the gas controls light 

and then one additional full turn (This is approximately 0.25'' 

W.C.). This will allow for dirty filters or any other slight static 

pressure increases in the system.

 manual reset High limit

The manual reset high limit switch is factory installed in place 

of the standard automatic reset high limit switch located in the 

duct furnace electrical junction box. In case of a failure of the 

blower motor, blockage of the inlet air, etc., the manual reset 

switch prevents the unit from cycling on the high limit. If the limit 

temperature is exceeded, a service person must inspect the unit for 

the cause of the high discharge temperature, take corrective action, 

and then reset the switch.

OPTIONAL 

CONTROL RELAY

IGNITION

CONTROLLER

CONTROL 

TRANSFORMER

LOW VOLTAGE

TERMINAL STRIP

SUPPLY 
POWER 

TERMINAL 

STRIP

OPTIONAL

DISCHARGE 

AIR T-STAT

POWER EXHAUSTER

RELAY

POWER 

EXHAUSTER 

MOTOR 

(HFP ONLY)

Summary of Contents for HFG Series

Page 1: ...er THIS MANUAL IS THE PROPERTY OF THE OWNER PLEASE BE SURE TO LEAVE IT WITH the owner WHEN YOU LEAVE THE JOB Inspection on Arrival 1 Inspect unit upon arrival In case of damage report it immediately t...

Page 2: ...etween blower and duct furnace to assure uniform air flow across the heat exchanger 3 To prevent premature heat exchanger failure the input to the appliance as indicated on the serial plate must not e...

Page 3: ...or 3 from bottom of sheet metal of unit casing Minimum clearance to combustible for HFP is 1 0 from rooftop Table 3 2 Combustible Material Clearances Table 3 3 Service Clearances HFP HFG 3 si metric...

Page 4: ...uctwork See Figure 4 3 Provide an airtight seal between the ductwork and the furnace Seams with cracks in ductwork should be caulked and or taped and be of permanent type All duct connections MUST be...

Page 5: ...ry supplied vent cap shipped loose fastened securely in place HFP units are shipped with the power exhauster discharge cover factory installed 3 For HFG units do not modify or obstruct the vent cap in...

Page 6: ...l to the unit casing In this case the gas piping must exit the unit through a side piping hole followed by the manual shut off valve piped back into the unit corner post through the unit bottom and le...

Page 7: ...ield installed manual gas shut off valve 11 Open the manual main gas valve on the combination gas control Call for heat with the thermostat and allow the pilot to light For HFP units on a call for hea...

Page 8: ...See Figure 9 1 To Adjust the Manifold Pressure 1 Move the field installed manual shut off valve to the OFF position 2 Remove the 1 8 pipe plug in the pipe tee and attach a water manometer of U tube ty...

Page 9: ...igure 19 1 for air shutter and heat exchanger support locations To decrease primary air move the air shutters away from the manifolds until flames no longer lift from burner ports but being careful no...

Page 10: ...ned and the main burner is lit to 50 fire 5 If the unit was provided with a time delay relay the blower starts after 30 to 45 seconds 6 If the temperature at the thermostat continues to fall the therm...

Page 11: ...r is lit to 100 full fire 5 If the unit was provided with a time delay relay the blower starts after 30 to 45 seconds 6 The modulating gas valve is controlled the BMS thermostat The thermostat can mod...

Page 12: ...arge air stream In case of elevated temperatures in the supply air the manual reset switch shuts down the entire unit If the limit temperature is exceeded a service person must inspect the unit for th...

Page 13: ...333 383 428 525 Weight Unit Net 207 225 248 288 318 400 Cap Net 16 16 16 16 26 35 Table 13 1 Model HFG Dimensions All dimensions in inches Figure 13 2 Rail or Slab Type Mounting Base A 33 50 10 26 DR...

Page 14: ...150 175 200 225 250 300 350 400 B 31 96 34 46 38 72 40 84 43 86 55 38 C 18 98 18 98 18 98 22 98 22 98 22 98 D 15 18 17 69 21 94 24 06 27 09 38 60 F 36 11 36 11 36 11 40 11 40 11 40 11 G 25 50 28 00 3...

Page 15: ...0 280 000 11111 6481 5185 4321 3989 3704 3457 3241 3050 2881 2729 2593 400 400 000 320 000 11111 7407 5926 4938 4558 4233 3951 3704 3486 3292 3119 2963 CFM Ratings are shown for elevations up to 2000...

Page 16: ...Furnace Pressure Drop vs CFM Curves 0 0 2 0 4 0 6 0 8 1 1 2 1 4 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 cfm Pressure DroP P W C 75 100 125 150 175 200 225 2...

Page 17: ...0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 cfm Pressure DroP P W C HFG 75 HFG100 125 HFG150 175 HFG200 225 HFG250 300 Caution Do n...

Page 18: ...cleaning these orifices To check the air shutters and main burner orifices see for Manifold Assembly Removal The heat exchanger should be checked annually for cracks and discoloration of the tubes If...

Page 19: ...order In replacing the burner be certain that the rear burner slots are located properly on the burner retaining pins Do not force the burner side access panel it will not fit if the burner is not pr...

Page 20: ...ked or worn c Replace ignition controller 8 Check all safety devices High limit air flow proving switch power exhauster centrifugal switch HFP Models Only gas pressure switches etc Determine and corre...

Page 21: ...t off a Gas controls wired incorrectly b Short circuit 3 Main gas pressure set too high 4 Defective gas valve 1 Power supply is off 2 No 24V power to thermostat 3 Thermostat malfunction 4 Defective po...

Page 22: ...EACH 1000 FEET OF ELEVATION ABOVE SEA LEVEL DESIGN COMPLIES WITH DUCT FURNACE STANDARD APPROVED FOR USE IN CA BY THE CEC WHEN EQUIPPED WITH IPI CERTIFIED TO CAN CSA C22 2 NO 236 DESIGN CONFORMS TO UL...

Page 23: ...F Single Stage M 2 stage or Modulating 9 Access Side AS R Right Hand L Left hand 10 Air Temperature Rise ATR H High 20 100 F L Low 20 60 11 Gas Type GT N Natural with continuous retry ignition control...

Page 24: ...YEARS FROM DATE OF SHIPMENT FROM SELLER These warranties are issued only to the original owner user and cannot be transferred or assigned No provision is made in these warranties for any labor allowa...

Reviews: