background image

5-571.4

88

start-uP ProceDure

Pilot burner adjustment

The pilot burner is orificed to burn properly with an inlet 

pressure of 6-7" W.C. on natural gas and 11-14" W.C. on 

propane gas, but final adjustment must be made after 

installation. If the pilot flame is too long or large, it is possible 

that it may cause soot and/or impinge on the heat exchanger 

causing failure. If the pilot flame is shorter than shown, it may 

cause poor ignition and result in the controls not opening the 

combination gas control. A short flame can be caused by a 

dirty pilot orifice. Pilot flame condition should be observed 

periodically to assure trouble-free operation.

to adjust the Pilot flame

1.  Create a call for heat from the thermostat.
2.  Remove the cap from the pilot adjustment screw. For 

location, see the combination gas control literature supplied 

with unit.

3.  Adjust the pilot length by turning the screw in or out 

to achieve a soft steady flame 3/4" to 1" long and 

encompassing 3/8"-1/2" of the tip of the thermocouple or 

flame sensing rod (See Figure 8.1).

4.  Replace the cap from the pilot adjustment screw.

figure 8.1 - correct Pilot flame 

main burner adjustment

The gas pressure regulator (integral to the combination gas 

control) is adjusted at the factory for average gas conditions. 

It is important that gas be supplied to the duct furnace in 

accordance with the input rating on the serial plate. Actual 

input should be checked and necessary adjustments made 

after the duct furnace is installed. Over-firing, a result of too 

high an input, reduces the life of the appliance and increases 

maintenance. Under no circumstances should the input exceed 

that shown on the serial plate.
Measuring the manifold pressure is done at the tee in the 

manifold (See Figure 9.1).

to adjust the manifold Pressure

1.  Move the field installed manual shut-off valve to the “OFF” 

position.

2.  Remove the 1/8" pipe plug in the pipe tee and attach a 

water manometer of “U” tube type which is at least 12" high.

3.  Move the field installed manual gas shut-off valve to the 

“ON” position.

4.  Create a high fire call for heat from the thermostat.
5.  Determine the correct high fire manifold pressure. For 

natural gas 3.5” W.C., for propane gas 10” W.C. Adjust the 

main gas pressure regulator spring to achieve the proper 

manifold pressure (for location, see the combination gas 

control literature supplied with unit).

6.  If the unit has Electronic Modulation gas controls 

(determine from the Model Identification Digit 12), the low 

fire gas pressure needs to be adjusted. Using Figure 9.2 for 

item number locations, this is accomplished as follows:

 

a.  Disconnect power.

 

b.  Remove all wires from duct furnace terminal “43” and 

 

remove cover plate (2).

 

c.  Turn on power at the disconnect switch.

 

d.  Remove the maximum adjustment screw (4), spring 

 

(5), and plunger (8). A small magnet is useful for this 

 

purpose. CAUTION - The plunger is a precision part. 

 

Handle carefully to avoid marring or picking up grease 

 

and dirt. Do not lubricate.

 

e.  Using minimum adjusting screw (9), adjust low fire 

 

manifold pressure to 0.56" W.C. for natural gas and    

 

1.6" W.C. for propane gas.

 

f.  Replace plunger and spring retainer, spring, and 

 

maximum adjusting screw in proper order.

 

g.  Using maximum adjustment screw (4), adjust high fire 

 

manifold pressure to 3.5" W.C. for natural gas and 10" 

 

W.C. for propane gas.

 

h.  Disconnect power.

 

i.  Replace cover plate (2) and re-install all wires from 

 

duct furnace terminal “43”.

7.  After adjustment, move the field installed manual shut-off 

valve to the “OFF” position and replace the 1/8" pipe plug.

8.  After the plug is in place, move the field installed manual 

shut-off valve to the “ON” position and recheck pipe plugs 

for gas leaks with soap solution.

3/4" to 1"

Summary of Contents for HFG Series

Page 1: ...er THIS MANUAL IS THE PROPERTY OF THE OWNER PLEASE BE SURE TO LEAVE IT WITH the owner WHEN YOU LEAVE THE JOB Inspection on Arrival 1 Inspect unit upon arrival In case of damage report it immediately t...

Page 2: ...etween blower and duct furnace to assure uniform air flow across the heat exchanger 3 To prevent premature heat exchanger failure the input to the appliance as indicated on the serial plate must not e...

Page 3: ...or 3 from bottom of sheet metal of unit casing Minimum clearance to combustible for HFP is 1 0 from rooftop Table 3 2 Combustible Material Clearances Table 3 3 Service Clearances HFP HFG 3 si metric...

Page 4: ...uctwork See Figure 4 3 Provide an airtight seal between the ductwork and the furnace Seams with cracks in ductwork should be caulked and or taped and be of permanent type All duct connections MUST be...

Page 5: ...ry supplied vent cap shipped loose fastened securely in place HFP units are shipped with the power exhauster discharge cover factory installed 3 For HFG units do not modify or obstruct the vent cap in...

Page 6: ...l to the unit casing In this case the gas piping must exit the unit through a side piping hole followed by the manual shut off valve piped back into the unit corner post through the unit bottom and le...

Page 7: ...ield installed manual gas shut off valve 11 Open the manual main gas valve on the combination gas control Call for heat with the thermostat and allow the pilot to light For HFP units on a call for hea...

Page 8: ...See Figure 9 1 To Adjust the Manifold Pressure 1 Move the field installed manual shut off valve to the OFF position 2 Remove the 1 8 pipe plug in the pipe tee and attach a water manometer of U tube ty...

Page 9: ...igure 19 1 for air shutter and heat exchanger support locations To decrease primary air move the air shutters away from the manifolds until flames no longer lift from burner ports but being careful no...

Page 10: ...ned and the main burner is lit to 50 fire 5 If the unit was provided with a time delay relay the blower starts after 30 to 45 seconds 6 If the temperature at the thermostat continues to fall the therm...

Page 11: ...r is lit to 100 full fire 5 If the unit was provided with a time delay relay the blower starts after 30 to 45 seconds 6 The modulating gas valve is controlled the BMS thermostat The thermostat can mod...

Page 12: ...arge air stream In case of elevated temperatures in the supply air the manual reset switch shuts down the entire unit If the limit temperature is exceeded a service person must inspect the unit for th...

Page 13: ...333 383 428 525 Weight Unit Net 207 225 248 288 318 400 Cap Net 16 16 16 16 26 35 Table 13 1 Model HFG Dimensions All dimensions in inches Figure 13 2 Rail or Slab Type Mounting Base A 33 50 10 26 DR...

Page 14: ...150 175 200 225 250 300 350 400 B 31 96 34 46 38 72 40 84 43 86 55 38 C 18 98 18 98 18 98 22 98 22 98 22 98 D 15 18 17 69 21 94 24 06 27 09 38 60 F 36 11 36 11 36 11 40 11 40 11 40 11 G 25 50 28 00 3...

Page 15: ...0 280 000 11111 6481 5185 4321 3989 3704 3457 3241 3050 2881 2729 2593 400 400 000 320 000 11111 7407 5926 4938 4558 4233 3951 3704 3486 3292 3119 2963 CFM Ratings are shown for elevations up to 2000...

Page 16: ...Furnace Pressure Drop vs CFM Curves 0 0 2 0 4 0 6 0 8 1 1 2 1 4 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 cfm Pressure DroP P W C 75 100 125 150 175 200 225 2...

Page 17: ...0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 cfm Pressure DroP P W C HFG 75 HFG100 125 HFG150 175 HFG200 225 HFG250 300 Caution Do n...

Page 18: ...cleaning these orifices To check the air shutters and main burner orifices see for Manifold Assembly Removal The heat exchanger should be checked annually for cracks and discoloration of the tubes If...

Page 19: ...order In replacing the burner be certain that the rear burner slots are located properly on the burner retaining pins Do not force the burner side access panel it will not fit if the burner is not pr...

Page 20: ...ked or worn c Replace ignition controller 8 Check all safety devices High limit air flow proving switch power exhauster centrifugal switch HFP Models Only gas pressure switches etc Determine and corre...

Page 21: ...t off a Gas controls wired incorrectly b Short circuit 3 Main gas pressure set too high 4 Defective gas valve 1 Power supply is off 2 No 24V power to thermostat 3 Thermostat malfunction 4 Defective po...

Page 22: ...EACH 1000 FEET OF ELEVATION ABOVE SEA LEVEL DESIGN COMPLIES WITH DUCT FURNACE STANDARD APPROVED FOR USE IN CA BY THE CEC WHEN EQUIPPED WITH IPI CERTIFIED TO CAN CSA C22 2 NO 236 DESIGN CONFORMS TO UL...

Page 23: ...F Single Stage M 2 stage or Modulating 9 Access Side AS R Right Hand L Left hand 10 Air Temperature Rise ATR H High 20 100 F L Low 20 60 11 Gas Type GT N Natural with continuous retry ignition control...

Page 24: ...YEARS FROM DATE OF SHIPMENT FROM SELLER These warranties are issued only to the original owner user and cannot be transferred or assigned No provision is made in these warranties for any labor allowa...

Reviews: