![Mobeye ThermoGuard TwinLog CML2255 Portal User Manual Download Page 24](http://html1.mh-extra.com/html/mobeye/thermoguard-twinlog-cml2255/thermoguard-twinlog-cml2255_portal-user-manual_1814836024.webp)
23
6. STATUS FEEDBACK
6.1 REQUEST ACTUAL TEMPERATURE
The actual temperature can be retrieved by sending a question mark as SMS text
message to the Mobeye CML2255, from any telephone and without code. This is only
possible when the CML2255 has external power (or in the program mode).
?
Upon sending the command, the Mobeye CML2255 returns an SMS text message to
the originator of the request.
6.2 OUTSIDE LED
The outside LED gives information of the status.
LED pattern
Status
Required action
Blinking green, 1 second
on / 1 second off
Module not configured
Configure at least one
telephone number.
1 green flash every 3
seconds
Module is switched on,
powered by batteries
No action required.
Green LED stays on
continuously
Module is switched on,
powered by an external
source
No action required.
Flashing red/ green
every second
Module establishes
network connection
Wait until the network
connection is established.
2 flashes red,
every 3 seconds
No GSM connection
Try the module at another
location.
3 flashes red,
every 3 seconds
No valid SIM card or
wrong PIN
SIM card failure.
Blinking 3 times green
Successful programming
action
No action required.
Blinking 5 times red
Faulty programming
action
Check SMS command.
4 red flashes
every 3 seconds
Low batteries
Replace both batteries.
Quickly flashing green
Module exchanges data
with portal
No action required