for pulse lines set cycle, according to the mode in which the slave clock operates:
H
half day, 12 hours (analog clock)
D
daily, 24 hours (digital clock)
pulse parameters for slave lines:
pulse
enter the pulse duration in tenths of seconds (01 - 99)
gap
enter the length of the gap between pulses in accelerated
mode in tenths of a seconds (01-99)
Default values for minute and half minute lines: pulse length 1.5 s, gap length 1.5 s
Default values for second line: pulse length 0.3 s, gap length 0.2 s
Note about setting a second line:
For a second line Σ imp + gap can’t be higher than 10 i = 10 no ast-forward mode is possible.
7.2 Setting the Line Status:
you can set the following line states:
run
the line starts
stop
the line stops
12pos-stop
the line runs to 12:00 in accelerated mode and then stop
If the MOBALine line type is set, stopping the line will set the analog slave clock
to 12:00 position.
7.3 Setting minute hand movement mode
The following modes can be set for MOBALine:
continuous
fluent hand movement
minute
hand moves in steps of one minute
½ minute
hand moves in steps of 1/2 minute
7.4 Offset setting
In line can be set to time shift lines versus time on the master clock - offset.
By default, the offset is set to 0.
By setting a negative / positive offset value, the time on the line is delayed / overtaken
by the value of the set offset,
eg at an offset value of -1.00 seconds, the time on the line is delayed by 1 second compared to
the time on the main clock.
Shift range -9.99 sec to +9.99 sec.
Adjust step by step:
sign sign
+/-
units of seconds
0-9
tens of milliseconds
0-99