80
GB MagFlux Manual 0812
Electromagnetic Flow Meter
Limitation of the automatic batch counter on DO 1 (opto relay)
The maximum limit is 500 pulses pr sec at 1 ms pulse length.
The formula for the minimum flow unit pr pulses is:
(flow at 20mA) x (pulse delay in mSec) / 1800000
Example: Min. flow unit/pulses for DN 100 max. flow 300 m3/h ?
Minimum flow unit pr pulses = 300 m
3
x 100 mSec / 1800000 =
0,016 m
3
which is rounded to 0,1 m
3
by the MagFlux.
The formula for the maximum flow unit pr pulses is:
(flow at 20mA)
Example: DN 100 max. flow 300 m
3
/h ?
Maximum flow unit pr pulses = 300 m
3
Limitation of the automatic batch counter on DO 2 (mech. relay)
The maximum limit is 120 pulses pr hour.
The formula for minimum flow unit pr pulses is:
(flow at 20mA) / 120
Example: DN 100 max. flow 300 m
3
/h ?
Minimum flow unit pr pulses = 300 / 120 = 2,5 m
3
The formula for maximum flow unit pr pulses is:
(flow at 20mA)
Example: DN 100 max. flow 300 m3/h ?
Maximum flow unit pr pulses = 300 m
3
Limitation of the manual and adaptive batch counter on DO 1 or DO 2
The formula for minimum flow unit pr pulses is:
(flow at 20mA) / 360
Example: DN 100 max. flow 300 m
3
/h ?
Minimum flow unit pr pulses = 300 / 360 = 0,833 m
3
Summary of Contents for MagFlux
Page 6: ...6 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...
Page 12: ...12 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...
Page 38: ...38 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...
Page 106: ...106 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...
Page 144: ...144 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...