![MJK MagFlux Installation And User Manual Download Page 24](http://html1.mh-extra.com/html/mjk/magflux/magflux_installation-and-user-manual_1812930024.webp)
24
GB MagFlux Manual 0812
Electromagnetic Flow Meter
Type 7300/7400 in Conductive Pipes
Conductive pipe
Potential equalization connection
Soft gasket
Conductive pipe
Ground connection.
NB! The flow sensor must be connected to an effective ground
connection, and the wire dimension must be at least 1.5 mm
2
.
Type 7300/7400 in Non-conductive Pipes
Ground connection.
NB! The flow sensor must be connected to an effective ground
connection, and the wire dimension must be at least 1.5 mm
2
.
Grounding ring (Min. thickness = 5 mm.)
Soft gasket
Non-conductive pipe
Potential equalization connection
Soft gasket
Non-conductive pipe