1-61
(7)
Standard operation data
(a)
Heat pump type
(220/240V)
Item
Model
SRK208HENF-L
SRK288HENF-L
SRK328HENF-L
SRK408HENF-L
Cooling
–
–
–
–
High pressure (kgf/cm
2
G)
Heating
15 ~ 17
17 ~ 19
17 ~ 19
18 ~ 20
Cooling
4.5 ~ 5.5
4 ~ 5
4.5 ~ 5.5
4 ~ 5
Low pressure (kgf/cm
2
G)
Heating
–
–
–
–
Cooling
14 ~ 16
11 ~ 15
12 ~ 16
12 ~ 16
Heating
16 ~ 18
18 ~ 22
18 ~ 22
18 ~ 22
Cooling
3.4/3.6
4.5/4.6
6.9/6.9
6.4/6.4
Running current (A)
Heating
3.0/3.4
4.0/4.1
6.1/6.1
6.5/6.5
(220V/240V)
Note (1) The data are measured at following conditions
Ambient air temperature
Indoor side:
Cooling ... 27
°
C DB, 19
°
C WB, Heating ... 20
°
C DB
Outdoor side:
Cooling ... 35
°
C DB, 24
°
C WB, Heating ... 7
°
C DB, 6
°
C WB
Temp. difference between suction
air and discharge air (˚C)
(b)
Cooling only type
(220/240V)
Item
Model
SRK208CENF-L
SRK258CENF-L
SRK288CENF-L
SRK328CENF-L
SRK408HENF-L
High pressure (kgf/cm
2
G)
–
–
–
–
–
Low pressure (kgf/cm
2
G)
5 ~ 6
5 ~ 6
4 ~ 5
5 ~ 6
4 ~ 5
11 ~13
12 ~ 16
13 ~ 17
12 ~ 16
13 ~ 17
Running current (A)
2.5/2.6
3.3/3.4
4.1/4.2
4.3/4.4
6.4/6.4
(220/240V)
Note (1) The data are measured at following conditions
Ambient air temperature
Indoor side:
27
°
C DB, 19
°
C WB
Outdoor side:
35
°
C DB, 24
°
C WB
Temp. difference between
suction air and discharge
air (˚C)
Summary of Contents for SRC208CENF-L
Page 26: ...Models SRK50A 56A...