1-6
Model SRK328HENF-L2 (Indoor unit)
SRC328HENF-L2 (Outdoor unit)
Item
Model
SRK328HENF
–
L2
SRC328HENF
–
L2
Cooling capacity
(1)
W
3000/3000
Heating capacity
(1)
W
3800/3800
Power source
1 Phase, 220/240V, 50Hz
Cooling input
kW
1.39/1.49
Running current (Cooling)
A
6.9/6.9
Heating input
kW
1.19/1.32
Running current (Heating)
A
6.1/6.1
Inrush current
A
33.6/36.6
COP (In cooling)
2.16/2.01
Noise level
(5)
dB(A)
Cooling: 40/42
Heating: 41/43
Cooling: 44/46
Heating: 45/47
Exterior dimensions
Height x Width x Depth
mm
275 x 790 x 174
542 x 795 x 255
Color
Ivory white
Polar white
Net weight
kg
8
37
Refrigerant equipment
Compressor type & Q’ty
–
RM5517GNE2 (Rotary type) x 1
MotorkW
–
1.3
Starting method
–
Line starting
Heat exchanger
Louver fins & bare tubing
Refrigerant control
Capillary tubes
Refrigerant
(4)
kg
R22
0.74
Refrigerant oil
R
0.6 (BARREL FREEZE 32SAM)
Defrost control
MC control
Air handling equipment
Fan type & Q’ty
Tangential fan x 1
Propeller fan x 1
MotorW
16
15
Air flow (at High)
(Cooling)
8.5/8.5
24/24.5
(Heating)
CMM
9.5/9.5
24/24.5
Air filter, Q’ty
Polypropylene net (washable) x 2
–
Shock & vibration absorber
–
Cushion rubber (for compressor)
Electric heater
–
–
Operation control
Operation switch
Wireless–Remote controller
–
Room temperature control
MC. Thermostat
–
Pilot lamp
RUN (Green), TIMER (Yellow)
–
Safety equipment
–
Dome mounted protector (for compressor)
Internal thermostat (for fan motor)
O.D
mm(in)
Liquid line: ø6.35 (1/4")
Gas line: ø12.7 (1/2")
Connecting method
Flare connecting
Attached length of piping
Liquid line: 0.4m
Gas line : 0.35m
–
Insulation
Necessary (Both sides)
Drain hose
Connectable
Power source cord
2.5m (3 cores with Earth)
Connection
Size x Core number
1.5mm
2
x 5 cores (Including earth cable)
wiring
Connecting method
Terminal block (Screw fixing type)
Accessories (included)
Mounting kit
Optional parts
–
Notes
(1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27ºC
19ºC
35ºC
24ºC
JIS C9612, ISO-T1
Heating
20ºC
–
7ºC
6ºC
JIS C9612, ISO-T1
(2) The operation data are applied to the 220V or 240V districts respectively
(3) Limitation of Voltage application
Minimum: 198V
Maximum: 264V
(4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping.
(Purging is not required even in the short piping.)
If the piping length is longer, when it is 10 m, add 20g refrigerant per meter and when it is 10 to 15m, add 30g refrigerant per meter.
(5) Expressed in sound pressure level.
Operation data
(1)
Refrigerant
piping
Summary of Contents for SRC208CENF-L