App - 50 App - 50
MELSEC-Q
APPENDICES
Special Register List (Continued)
ACPU
Special
Conversion
Special
Register after
Conversion
Special
Register for
Modification
Name
Meaning
Details
Corresponding
CPU
D9124
SD1124
SD63
Annunciator
detection
quantity
Annunciator
detection quantity
• When one of F0 to 255 (F0 to 2047 for AuA and AnU)
is turned on by SET F 1 is added to the contents of
SD63. When RST F or LEDR instruction is
executed, 1 is subtracted from the contents of SD63.
(If the INDICATOR RESET switch is provided to the
CPU, pressing the switch can execute the same
processing.)
• Quantity, which has been turned on by SET F is
stored into SD63 in BIN code. The value of SD63 is
maximum 8.
D9125
SD1125
SD64
D9126
SD1126
SD65
D9127
SD1127
SD66
D9128
SD1128
SD67
D9129
SD1129
SD68
D9130
SD1130
SD69
D9131
SD1131
SD70
D9132
SD1132
SD71
Annunciator
detection
number
Annunciator
detection number
• When one of F0 to 255 (F0 to 2047 for AuA and AnU)
is turned on by SET F , F number, which has turned
on, is entered into SD64 to SD71 in due order in BIN
code.
• F number, which has been turned off by RST F , is
erased from SD64 to SD71, and the contents of data
registers succeeding the data register, where the
erased F number was stored, are shifted to the
preceding data registers.
• By executing LEDR instruction, the contents of
SD64 to SD71 are shifted upward by one. (For A3N,
A3HCPU, it can be performed by use of INDICATOR
RESET switch on front of CPU module.)
• When there are 8 annunciator detections, the 9th one
is not stored into SD64 to SD71 even if detected.
0
50 50 50 50 50 50 50 50 50 50 50 99
0
0
50 50 50 50 50 50 50 50 50 50 99
0
25 25 99 99 99 99 99 99 99 99 15
1
2
3
2
3
4
5
6
7
8
8
8
50
0
0
99
15 15 15 15 15 15 15 70
0
0
0
0
70 70 70 70 70 70 65
0
0
0
0
0
0
65 65 65 65 65 38
0
0
0
0
0
0
0
38 38 38 38 110
0
0
0
0
0
0
0
0
110 110 110 151
0
0
0
0
0
0
0
0
151 151 210
0
0
0
0
0
0
0
0
0
0
SD62
SD63
SD64
SD65
SD66
SD67
SD68
SD69
SD70
SD71
SET
F50
SET
F25
SET
F99
RST
F25
SET
F15
SET
F70
SET
F65
SET
F38
SET
F110
SET
F151
SET
F210 LEDR