10 - 52 10 - 52
MELSEC-Q
10 DEVICES
10.8 Nesting (N)
(1) Definition
Nesting devices are used to nest MC or MCR master control instructions when
programming operating conditions.
(2) Designation method with master control
The master control instructions are used to open and close the ladders' common
bus so that switching of ladders may be executed efficiently by the sequence
program.
Nesting devices must be numbered in descending order (from N0 to N7) of
nested relation.
For details on how to use master control, refer to the QCPU(Q mode)/QnACPU
Programming Manual (Common Instructions).
N0
nesting
control range
N1
nesting
control range
N2
nesting
control range
Executed when conditions
"A" and "B" are satisfied.
Executed when condition
"A" is satisfied.
M15
N0
B
C
A
M15
N0
MC
M16
N1
MC
N2
MCR
N1
MCR
M17
N2
MC
N0
M16
N1
M17
N2
Executed when condition "
A", "B" and "C" are satisfied.
N1 is reset.
Executed when conditions
"A" and "B" are satisfied.
N1 to 2 are reset.
Executed when condition
"A" is satisfied.
N0 to 2 are reset.
Designated in ascending
No. order
Designated in descending
No. order
Executed regardless of
A, B, C condition statuses.
MCR