1. OVERVIEW

This user's manual provides the specifications, handling, part names and

others of the Q64TD thermocouple temperature input module (abbreviated to
the Q64TD) and Q64TDV-GH channel isolated thermocouple/micro voltage

input module (abbreviated to the Q64TDV-GH) used with the MELSEC-Q

series CPU module.

2. SPECIFICATIONS

The following are the specifications of the Q64TD/Q64TDV-GH.

2.1 Specifications of Q64TD
2.1.1 Performance Specifications

Item

Specifications

Number of channels

4 channels

Temperature
conversion value

16-bit, signed binary

(-2700 to 18200: Value to the first decimal place     10 times)

Out
put

Scaling value

16-bit, signed binary

Standard with which
thermocouple conforms

JIS C1602-1995

Usable thermocouples and
measured temperature range
accuracies

Refer to Section 2.1.2

Cold junction temperature
compensation accuracy

1.0

Accuracy

As per calculation expression marked *1

Resolution

B,R,S,N : 0.3          K,E,J,T : 0.1

Conversion speed

40ms/channel *2

Number of analog input
points

4 ch Pt100 connection channel/module

Insulation system

Across thermocouple input and earth
Across thermocouple input channels
Across cold junction temperature compensation input
(Pt100) and earth

: Transformer insulation
: Transformer insulation
: No insulation

Dielectric withstand voltage

1780VrmsAC/3 cycles (altitude 2000m)

Insulation resistance

Across thermocouple input and earth

Across thermocouple input channels

: 500VDC 100M

 or more using

insulation resistance tester

: 500VDC 10M

 or more using

insulation resistance tester

Wire break detection

Yes (Each channel independent) *3

E

2

PROM write count

Max. 100 thousand times

Number of occupied points

16 points

Connection terminals

18-point terminal block

Applicable wire size

0.3 to 0.75mm

2

Applicable crimping terminals

1.25-3  R1.25-3(Sleeved crimping terminals are unusable)

Internal current consumption
(5VDC)

0.50A

Weight

0.25kg

Outline dimensions

98(H)   27.4(W)   90(D)mm

*1: Calculate the accuracy in the following method.

(Accuracy) = (conversion accuracy) + (temperature characteristic)   (operating ambient temperature
variation) + (cold junction temperature compensation accuracy)
An operating ambient temperature variation indicates a deviation of the operating ambient
temperature from the 25 5

 range.

Example: When the thermocouple used is B, the operating ambient temperature is 35 , and
the measured temperature is 1000 , the accuracy is:

 ( 2.5 ) + ( 0.4 )   (5 ) + ( 1 ) =  5.5

*2: The conversion speed is a period from when a temperature is input and converted into a

corresponding digital value until the value is stored into the buffer memory. When two or more
channels are used, the conversion speed is "40ms   number of conversion enabled channels".

*3: At wire break detection, the temperature measurement value right before wire break occurrence is held.

Summary of Contents for Q64TD

Page 1: ...OLLER User s Manual Hardware Q64TD Q64TDV GH Thank you for purchasing the Mitsubishi general purpose programmable logic controller MELSEC Q series Prior to use please read this manual thoroughly and familiarize yourself with the product MODEL Q64TD U H JE MODEL CODE 13JT30 IB NA 0800155 B 0201 MEE 2000 MITSUBISHI ELECTRIC CORPORATION ...

Page 2: ...d by CAUTION may also be linked to serious results In any case it is important to follow the directions for usage Store this manual in a safe place so that you can take it out and read it whenever necessary Always forward it to the end user DESIGN PRECAUTIONS DANGER Do not write data into the system area of the buffer memory of intelligent function modules Also do not use any prohibited to use sig...

Page 3: ...or the module resulting in fallout short circuits or malfunction Switch all phases of the external power supply off when mounting or removing the module Not ding so may cause electric shock or damage to the module Do not directly touch the conductive area or electronic components of the module Doing so may cause malfunction or failure in the module WIRING PRECAUTIONS CAUTION Always ground the FG t...

Page 4: ...t Not doing so will make the module more susceptible to noises surges and inductions REVISIONS The manual number is given on the bottom right of the top cover Print Date Manual Number Revision Nov 2000 IB NA 0800155 A First edition Jan 2002 IB NA 0800155 B Model Q64TDV GH was added Addition Section2 2 Correction About the Manuals Chapter1 Section2 1 Chapter4 Section5 1 Section5 2 Section5 3 Chapte...

Page 5: ...red temperature range accuracies 2 2 2 Specifications of Q64TDV GH 3 2 2 1 Performance specifications 3 2 2 2 Usable thermocouples and measured temperature range accuracies 5 2 2 3 Micro voltage input range and accuracies 5 3 LOADING AND INSTALLATION 6 3 1 Handling Instructions 6 3 2 Installation Environment 6 4 NAMES AND SETTINGS OF THE PARTS 7 5 WIRING 8 5 1 Wiring Instructions 8 5 2 External Wi...

Page 6: ...64TDV GH GX Configurator TI SW1D5C QTIU E SH 080141 13JR30 Conformance to the EMC Directive Low Voltage Directive For details on making Mitsubishi PLC conform to the EMC directive and low voltage instruction when installing it in your product please see Chapter 3 EMC Directive and Low Voltage Instruction of the User s Manual Hardware of the PLC CPU to use The CE logo is printed on the rating plate...

Page 7: ...tage 1780VrmsAC 3 cycles altitude 2000m Insulation resistance Across thermocouple input and earth Across thermocouple input channels 500VDC 100MΩ or more using insulation resistance tester 500VDC 10MΩ or more using insulation resistance tester Wire break detection Yes Each channel independent 3 E 2 PROM write count Max 100 thousand times Number of occupied points 16 points Connection terminals 18 ...

Page 8: ... value of 0 5 and 0 25 of measured temperature Larger value of 0 06 and 0 02 of measured temperature 6 75 E 900 to 1000 3 3 3 210 to 40 3 3 3 40 to 750 2 Larger value of 0 5 and 0 25 of measured temperature Larger value of 0 06 and 0 02 of measured temperature 5 625 J 750 to 1200 3 3 3 270 to 200 3 3 3 200 to 0 2 Larger value of 0 5 and 0 5 of measured temperature Larger value of 0 06 and 0 1 of m...

Page 9: ...hannels Across cold junction temperature compensation input Pt100 and earth Transformer insulation Transformer insulation No insulation Dielectric withstand voltage 1780VrmsAC 3 cycles altitude 2000m Insulation resistance Across thermocouple input micro voltage input and earth Across thermocouple input micro voltage input channels 500VDC 100MΩ or more using insulation resistance tester 500VDC 10MΩ...

Page 10: ... into the buffer memory The conversion speed is a delay time that occurs during sampling processing It is independent of averaging processing Example When two channels are enabled for conversion Conversion speed sampling period 3 20ms 2 channels 3 120ms CH 1 CH 2 Input 1 Conversion speed Conversion processing Buffer memory Input 2 CH 1 CH 2 CH 1 CH 2 CH 1 CH 2 CH 1 CH 2 Input 1 Input 2 Conversion ...

Page 11: ... 5 25 200 to 900 2 2 0 0 15 5 75 E 900 to 1000 3 3 3 210 to 40 3 3 3 40 to 200 2 1 5 5 25 200 to 750 2 2 0 0 15 5 75 J 750 to 1200 3 3 3 270 to 200 3 3 3 200 to 0 2 2 0 4 5 0 to 350 2 1 5 0 1 4 0 T 350 to 400 3 3 3 270 to 200 3 3 3 200 to 0 2 2 5 8 75 0 to 200 2 2 0 8 25 0 to 1250 2 2 5 0 25 8 75 N 1250 to 1300 3 3 3 1 If a value entered from the thermocouple is outside the measured temperature ra...

Page 12: ...evention label at its top During wiring do not remove this label For system operation always remove this label to ensure adequate heat dissipation 5 Tighten the mounting and terminal screws of the module within the following ranges Screw Location Tightening Torque Range Module mounting screw M3 screw 36 to 48 N cm Terminal block terminal screw M3 screw 42 to 58 N cm Terminal block mounting screw M...

Page 13: ...Q64TDV GH Number Name and Appearance Description 1 RUN LED Indicates the operating status of the Q64TD Q64TDV GH On Operating normally Flicker Offset gain setting mode Off 5V power off Watchdog timer error occurrence or module change enabled status during online module change 2 ERR LED Indicates the error status of the Q64TD Q64TDV GH On Error occurrence Flicker Switch setting error Switch 5 was s...

Page 14: ...inverter s load circuit Not doing so will make the module more susceptible to noises surges and inductions 3 Insulation sleeved crimping terminals cannot be used with the terminal block It is recommended to fit mark tubes or insulation tubes to the wire connection parts of the crimping terminals 5 2 External Wiring 1 Thermocouple RTD Input amplifier CH1 Filter Transformer CH4 Pt100 1 2 1 As cables...

Page 15: ...er CH4 Pt100 1 2 1 As cables always use shielded conductors Also wire the shielded cables as short as possible 2 Always connect to the earth terminal of the control box SLD SLD FG Input amplifier Input amplifier Filter Transformer Load cell or like Load cell or like ...

Page 16: ...e B 4 Thermocouple R 5 Thermocouple S 6 Thermocouple N 7 Micro voltage input 8 Switch 1 Input type setting CH4 CH3 CH2 CH1 H Offset gain setting Set value Factory setting 0 User setting 1 Switch 2 Offset gain setting CH4 CH3 CH2 CH1 H Switch 3 Empty Switch 4 H 0H With cold junction temperature compensation 1 to FH Without cold junction temperature compensation 0H Normal mode 1 to FH Offset gain se...

Page 17: ...H1 CH2 1 2 SLD SLD CH3 CH4 3 4 SLD SLD FG Q64TD 2 0 08 112 4 41 98 3 86 105 4 14 2 0 08 5 0 20 Unit mm in 2 Q64TDV GH 27 4 1 08 Q64TDV GH RUN ERROR 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 R T D CH1 CH2 1 2 SLD SLD CH3 CH4 3 4 SLD SLD FG Q64TDV GH 2 0 08 112 4 41 98 3 86 105 4 14 2 0 08 5 0 20 Unit mm in ...

Page 18: ... V Spanish Branch Carretera de Rubi 76 80 08190 Sant Cugat del Valles Barcelona Spain Tel 34 935 653135 South Africa Circuit Breaker Industries LTD Private Bag 2016 Isando 1600 Johannesburg South Africa Tel 27 11 928 2000 Hong Kong Ryoden Automation Ltd 10th Floor Manulife Tower 169 Electric Road North Point HongKong Tel 852 2887 8870 China Ryoden International Shanghai Ltd 3F Block5 Building Auto...

Reviews: