5
2.2.2 Usable Thermocouples and Measured Temperature Range Accuracies
Usable
Thermo
couple
Type
Measured
Temperature
Range*1
Conversion Accuracy
(At operating ambient
temperature
25 5
)
Temperature Characteristic
(Per operating ambient
temperature variation of 1 )
Max. Temperature
Error at Ambient
Temperature 55
0 to 600
——— *3
——— *3
——— *3
600 to 800
*2
4.0
14.0
800 to 1700
*2
3.5
0.4
13.5
B
1700 to 1820
——— *3
——— *3
——— *3
-50 to 0
——— *3
——— *3
——— *3
0 to 300
*2
4.0
14.0
300 to 1600
*2
3.5
0.4
13.5
R
1600 to 1760
——— *3
——— *3
——— *3
-50 to 0
——— *3
——— *3
——— *3
0 to 300
*2
4.0
14.0
300 to 1600
*2
3.5
0.4
13.5
S
1600 to 1760
——— *3
——— *3
——— *3
-270 to -200
——— *3
——— *3
——— *3
-200 to 0
*2
2.0
8.25
0 to 200
*2
1.5
7.75
0 to 1200
*2
2.0
0.25
8.25
K
1200 to 1370
——— *3
——— *3
——— *3
-270 to -200
——— *3
——— *3
——— *3
-200 to 200
*2
1.5
5.25
200 to 900
*2
2.0
0.15
5.75
E
900 to 1000
——— *3
——— *3
——— *3
-210 to -40
——— *3
——— *3
——— *3
-40 to 200
*2
1.5
5.25
200 to 750
*2
2.0
0.15
5.75
J
750 to 1200
——— *3
——— *3
——— *3
-270 to -200
——— *3
——— *3
——— *3
-200 to 0
*2
2.0
4.5
0 to 350
*2
1.5
0.1
4.0
T
350 to 400
——— *3
——— *3
——— *3
-270 to -200
——— *3
——— *3
——— *3
-200 to 0
*2
2.5
8.75
0 to 200
*2
2.0
8.25
0 to 1250
*2
2.5
0.25
8.75
N
1250 to 1300
——— *3
——— *3
——— *3
*1: If a value entered from the thermocouple is outside the measured temperature range given in the table, it is
handled as the maximum/minimum value of the measured temperature range.
*2: The accuracies only in the temperature ranges of Class 1 to 3 (shaded areas) in JIS C1602-1995 apply.
*3: Temperature measurement can be made, but accuracy is not guaranteed.
2.2.3 Micro voltage input range and accuracies
Conversion Accuracy
Input Type
Measurable Voltage
Range
(At 25 5
operating ambient
temperature)
(At 0 to 55
operating ambient
temperature)
Micro voltage input
-100 to 100mV
0.2mV
0.8mV