2.1.2 Usable Thermocouples and Measured Temperature Range Accuracies
Usable
Thermo
couple
Type
Measured
Temperature
Range*1
Conversion Accuracy
(At operating ambient
temperature
25 5
)
Temperature Characteristic
(Per operating ambient
temperature variation of 1 )
Max. Temperature
Error at Ambient
Temperature 55
0 to 600
——— *3
——— *3
——— *3
600 to 800
*2
3.0
13.0
800 to 1700
*2
2.5
0.4
12.5
B
1700 to 1820
——— *3
——— *3
——— *3
-50 to 0
——— *3
——— *3
——— *3
0 to 300
*2
2.5
0.4
12.5
300 to 1600
*2
2.0
0.3
9.5
R
1600 to 1760
——— *3
——— *3
——— *3
-50 to 0
——— *3
——— *3
——— *3
0 to 300
*2
2.5
0.4
12.5
300 to 1600
*2
2.0
0.3
9.5
S
1600 to 1760
——— *3
——— *3
——— *3
-270 to -200
——— *3
——— *3
——— *3
-200 to 0
*2
Larger value of 0.5 and
0.5% of measured
temperature
Larger value of 0.06 and
0.2% of measured
temperature
11.0
0 to 1200
*2
Larger value of 0.5 and
0.25% of measured
temperature
Larger value of 0.06 and
0.02% of measured
temperature
9.0
K
1200 to 1370
——— *3
——— *3
——— *3
-270 to -200
——— *3
——— *3
——— *3
-200 to 0
*2
Larger value of 0.5 and
0.5% of measured
temperature
Larger value of 0.06 and
0.15% of measured
temperature
8.5
0 to 900
*2
Larger value of 0.5 and
0.25% of measured
temperature
Larger value of 0.06 and
0.02% of measured
temperature
6.75
E
900 to 1000
——— *3
——— *3
——— *3
-210 to -40
——— *3
——— *3
——— *3
-40 to 750
*2
Larger value of 0.5 and
0.25% of measured
temperature
Larger value of 0.06 and
0.02% of measured
temperature
5.625
J
750 to 1200
——— *3
——— *3
——— *3
-270 to -200
——— *3
——— *3
——— *3
-200 to 0
*2
Larger value of 0.5 and
0.5% of measured
temperature
Larger value of 0.06 and
0.1% of measured
temperature
6.0
0 to 350
*2
Larger value of 0.5 and
0.25% of measured
temperature
Larger value of 0.06 and
0.02% of measured
temperature
2.625
T
350 to 400
——— *3
——— *3
——— *3
-270 to -200
——— *3
——— *3
——— *3
-200 to 0
*2
Larger value of 0.5 and
0.5% of measured
temperature
Larger value of 0.06 and
0.2% of measured
temperature
11.0
0 to 1250
*2
Larger value of 0.5 and
0.25% of measured
temperature
Larger value of 0.06 and
0.02% of measured
temperature
9.375
N
1250 to 1300
——— *3
——— *3
——— *3
*1: If a value entered from the thermocouple is outside the measured temperature range given in the table, it is
handled as the maximum/minimum value of the measured temperature range.
*2: The accuracies only in the temperature ranges of Class 1 to 3 (shaded areas) in JIS C1602-1995 apply.
*3: Temperature measurement can be made, but accuracy is not guaranteed.