2.2 Specifications of Q64TDV-GH
2.2.1 Performance Specifications
Item
Specifications
Number of channels
4 channels
Temperature
conversion value
16-bit, signed binary
(-2700 to 18200: Value to the first decimal place 10 times)
Micro voltage
conversion value
16-bit signed binary (-25000 to 25000)
Out
put
Scaling value
16-bit, signed binary
Standard with which
thermocouple conforms
JIS C1602-1995
Usable thermocouples and
measured temperature range
accuracies
Refer to Section 2.2.2
Cold junction temperature
compensation accuracy
1.0
Thermocouple input
accuracy
As per calculation expression marked *1
Micro voltage input range
-100mV to +100mV (input resistance 2M
Ω
or more)
Micro voltage input accuracy
Refer to Section 2.2.3.
Thermocouple
input
B:0.7
R,S:0.8 K,T:0.3 E:0.2
J:0.1 N:0.4
Resolution
Micro voltage
input
4 V
Sampling period
20ms/channel *2
Conversion speed
Sampling period 3*3
Number of analog input
points
4 ch Pt100 connection channel/module
Absolute maximum input
5V
Insulation system
Across thermocouple input/micro voltage input and
earth
Across thermocouple input/micro voltage input
channels
Across cold junction temperature compensation input
(Pt100) and earth
: Transformer insulation
: Transformer insulation
: No insulation
Dielectric withstand voltage
1780VrmsAC/3 cycles (altitude 2000m)
Insulation resistance
Across thermocouple input/micro
voltage input and earth
Across thermocouple input/micro
voltage input channels
: 500VDC 100M
Ω
or more using
insulation resistance tester
: 500VDC 10M
Ω
or more using
insulation resistance tester
Wire break detection
Yes (Each channel independent) *4
E
2
PROM write count
Max. 100 thousand times
Number of occupied points
16 points
Connection terminals
18-point terminal block
Applicable wire size
0.3 to 0.75mm
2
Applicable crimping terminals
1.25-3 R1.25-3(Sleeved crimping terminals are unusable)
Internal current consumption
(5VDC)
0.50A
Weight
0.25kg
Outline dimensions
98(H) 27.4(W) 112(D)mm
*1: Calculate the accuracy in the following method.
(Accuracy) = (conversion accuracy) + (temperature characteristic) (operating ambient temperature
variation) + (cold junction temperature compensation accuracy)
An operating ambient temperature variation indicates a deviation of the operating ambient
temperature from the 25 5
range.
Example: When the thermocouple used is B, the operating ambient temperature is 35 , and
the measured temperature is 1000 , the accuracy is:
( 3.5 ) + ( 0.4 ) (5 ) + ( 1 ) = 6.5