4
*2: A period until a thermocouple input value/micro voltage input value is converted
into a temperature
measurement value/micro voltage conversion value.
*3: A period until a thermocouple input value/micro voltage input value is converted into a
temperature measurement value/micro voltage conversion value and the resultant value is stored
into the buffer memory.
The conversion speed is a delay time that occurs during sampling processing. It is independent of
averaging processing.
Example: When two channels are enabled for conversion
(Conversion speed) = (sampling period) 3
= (20ms 2 channels) 3
= 120ms
CH.1
CH.2
Input 1)
Conversion speed
Conversion processing
Buffer memory
Input 2)
CH.1
CH.2
CH.1
CH.2
CH.1
CH.2
CH.1
CH.2
Input 1)
Input 2)
Conversion speed
*4:At wire break detection, the temperature measurement value/micro voltage conversion value right
before wire break occurrence is held.