114
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
6000
The control system and standby system
in the redundant system do not have
the same programs and parameters.
(This can be detected from the standby
system of the redundant system.)
Synchronise the programs and
parameters of the control system and
standby system.
Q4AR
6010
The operational status of the control
system and standby system in the
redundant system is not the same.
(This can be detected from the standby
system of the redundant system.)
Synchronise the operation statuses of
the control system and standby system.
Q4AR
6100
A CPU module tracking memory error
was detected during initial.
(This can be detected from the control
system or standby system of the
redundant system.)
Hardware fault of the CPU module.
(Please contact your local nearest
Mitsubishi or sales representative,
explaining a detailed description of the
problem. Change the CPU modules in
order of the standby system CPU
module and control system CPU
module.)
Q4AR
6101
The CPU module detected an error
during the handshake for tracking.
(This can be detected from the control
system or standby system of the
redundant system.)
Check the condition of the other
stations.
Q4AR
6200
The standby system in a redundant
system is switched to the control
system.
(This can be detected from the standby
system of the redundant system.)
Check the control system condition.
Q4AR
6210
The control system in a redundant
system is switched to the standby
system.
(This can be detected from the standby
system of the redundant system.)
Check the control system condition.
Q4AR