96
3103
• Although the number of modules has
been set to one or greater number in
the Ethernet module count
parameter setting, the number of
actually mounted module is zero.
• The start I/O No. of the Ethernet
network parameter differs from the I/
O No. of the actually mounted
module.
• Correct and write the network
parameters.
• If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
QnA
• AJ71QE71 does not exist in the
position of I/O number set by the
parameter.
• I/O number designation is
overlapping.
• Numbers of the network parameter
and loaded AJ71QE71 are different.
• Ethernet (par dedicated
instruction) is set to more than five.
QnA
3104
• The Ethernet and MELSECNET/10
use the same network number.
• The network number, station number
or group number set in the network
parameter is out of range.
• The specified I/O number is outside
the range of the used CPU module.
• The Ethernet-specific parameter
setting is not normal.
• Correct and write the network
parameters.
• If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
QnA
3105
The contents of the Ethernet parameter
are incorrect.
Write after correcting parameters.
QnA
3107
• The CC-Link parameter setting is
incorrect.
• The set mode is not allowed for the
version of the mounted CC-Link
module.
Check the parameter setting.
QnA
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU