66
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
1000
Runaway or failure of CPU module or
failure of main CPU
• Malfunctioning due to noise or other
reason
• Hardware fault
• Take noise reduction measures.
• Reset the CPU module and RUN it
again.If the same error is displayed
again, this suggests a CPU module
hardware fault.(Contact your local
Mitsubishi representative.)
QnA
1010
Entire program was executed without
the execution of an END instruction.
• When the END instruction is
executed it is read as another
instruction code, e.g. due to noise.
• The END instruction has been
changed to another instruction code
somehow.
• Take noise reduction measures.
• Reset the CPU module and RUN it
again. If the same error is displayed
again, this suggests a CPU module
hardware fault. (Contact your local
Mitsubishi representative.)
QnA