background image

8

GB

D

F

I

NL

E

P

GR

RU

TR

9

Always insulate the piping properly.  Insufficient insulation will result in a de-
cline in heating/cooling performance, water drops from condensation and other
such problems.

0

When connecting the refrigerant piping, make sure the ball valve of the out-
door unit is completely closed (the factory setting) and do not operate it until
the refrigerant piping for the outdoor and indoor units has been connected, a
refrigerant leakage test has been performed and the evacuation process has
been completed.

A

Always use a non-oxidizing brazing material for brazing the parts.  If a non-
oxidizing brazing material is not used, it could cause clogging or damage to
the compressor unit.

B

Never perform outdoor unit piping connection work when it is raining.

 Warning:

When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-

function and result in severe damage.

 Caution:

Use a vacuum pump with a reverse flow check valve.

- If the vacuum pump does not have a reverse flow check valve, the vacuum

pump oil may flow back into the refrigerant cycle and cause deterioration of
the refrigerator oil and other trouble.

Do not use the tools shown below used with conventional refrigerant.
(Gauge manifold, charge hose, gas leak detector, check valve, refrigerant
charge base, vacuum gauge, refrigerant recovery equipment)

- Mixing of conventional refrigerant and refrigerator oil may cause the refrig-

erator oil to deteriorate.

- Mixing of water will cause the refrigerator oil to deteriorate.
- R407C refrigerant does not contain any chlorine. Therefore, gas leak detec-

tors for conventional refrigerants will not react to it.

Manage the tools more carefully than normal.

- If dust, dirt, or water gets in the refrigerant cycle, the refrigerator oil will dete-

riorate.

Never use existing refrigerant piping.

- The large amount of chlorine in conventional refrigerant and refrigerator oil

in the existing piping will cause the new refrigerant to deteriorate.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.

- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and

the compressor may fail.

Do not use a charging cylinder.

- Using a charging cylinder may cause the refrigerant to deteriorate.

Do not use special detergents for washing piping.

7.2. Refrigerant piping system

Connection Example

[Fig. 7.2.1]

 

(P.3)

Å

Liquid pipe

ı

Gas pipe

Ç

Total capacity of indoor units

Î

Model number

Downstream Unit Model Total

Ï

Branch Kit Model

Ì

4-Branching Header

Ó

7-Branching Header

¬

10-Branching Header

A

Outdoor Unit

B

First Branch

C

Indoor unit

D

Cap

The pipe of 28.58 mm can be used for the gas pipe of PU(H)Y-P200.

The pipe of 34.93 mm can be used for the gas pipe of PU(H)Y-P315.

8. Additional Refrigerant Charge

At the time of shipping, the outdoor unit is charged with the refrigerant.  As this
charge does not include the amount needed for extended piping, additional charg-
ing for each refrigerant line will be required on site.  In order that future servicing
may be properly provided, always keep a record of the size and length of each
refrigerant line and the amount of additional charge by writing it in the space pro-
vided on the outdoor unit.

8.1. Calculation of Additional Refrigerant

Charge

Calculate the amount of additional charge based on the length of the piping
extension and the size of the refrigerant line.

Use the table to the right as a guide to calculating the amount of additional
charging and charge the system accordingly.

If the calculation results in a fraction of less than 0.1 kg, round up to the next
0.1 kg.  For example, if the result of the calculation was 12.62 kg, round the
result up to 12.7 kg.

<Additional Charge>

=

+

+

α

8.2. Precautions concerning piping connec-

tion and valve operation

Conduct piping connection and valve operation accurately.

The gas side connecting pipe is assembled in factory before shipment.

1

For brazing to the connecting pipe with flange, remove the connecting pipe
with flange from the ball valve, and braze it outside of the unit.

2

During the time when removing the connecting pipe with flange, remove
the seal attached on the rear side of this sheet and paste it onto the flange
surface of the ball valve to prevent the entry of dust into the valve.

3

The refrigerant circuit is closed with a round, close-packed packing upon
shipment to prevent gas leak between flanges. As no operation can be
done under this state, be sure to replace the packing with the hollow pack-
ing attached at the piping connection.

4

At the mounting of the hollow packing, wipe off dust attached on the flange
sheet surface and the packing. Coat refrigerating machine oil (Ester oil,
ether oil or alkylbenzene [small amount]) onto both surfaces of the pack-
ing.

[Fig. 8.2.1] (P.3)

After evacuation and refrigerant charge, ensure that the handle is fully open. If
operating with the valve closed, abnormal pressure will be imparted to the
high- or low-pressure side of the refrigerant circuit, giving damage to the com-
pressor, four-way valve, etc.

Determine the amount of additional refrigerant charge by using the formula,
and charge refrigerant additionally through the service port after completing
piping connection work.

After completing work, tighten the service port and cap securely not to gener-
ate gas leak.

[Fig. 8.2.2] (P.3)

<A> [Ball valve (gas side)] (This figure shows the valve in the fully open state.)

<B> [Ball valve (liquid side)]

A

Valve stem
[Fully closed at the factory, when connecting the piping, when evacuating, and
when charging additional refrigerant. Open fully after the operations above are
completed.]

B

Stopper pin [Prevents the valve stem from turning 90

°

 or more.]

C

Packing (Accessory)
[Manufacturer: Nichiasu corporation]
[Type: T/#1991-NF]

D

Connecting pipe (Accessory)
[Use packing and securely install this pipe to the valve flange so that gas leakage
will not occur. (Tightening torque: 25 N·m) Coat both surfaces of the packing with
refrigerating machine oil. (Ester oil, ether oil or alkylbenzene [small amount])]

E

Open (Operate slowly)

F

Cap, copper packing

Liquid pipe size
Total length of
ø6.35 

×

 0.024

(m) 

×

 0.024 (kg/m)

Liquid pipe size
Total length of
ø9.52 

×

 0.06

(m) 

×

 0.06 (kg/m)

Additional
refrigerant charge

                        (kg)

At the
conditions
below:

Liquid pipe size
Total length of
ø12.7 

×

 0.12

(m) 

×

 0.12 (kg/m)

<Example>
Indoor 1: 40

A: ø12.7

40 m

a: ø6.35

10 m

2: 100

B: ø12.7

10 m

b: ø9.52

5 m

3: 40

C: ø12.7

15 m

c: ø6.35

10 m

4: 32

D: ø12.7

10 m

d: ø6.35

10 m

5: 63

e: ø9.52

10 m

The total length of each liquid line is as follows:
ø12.7: A + B + C + D = 40 + 10 + 15 + 10 = 75 m
ø9.52: b + e = 5 + 10 = 15 m
ø6.35: a + c + d = 10 + 10 + 10 = 30 m
Therefore,
<Calculation example>
Additional refrigerant charge

= 75 

×

 0.12 + 15 

×

 0.06 + 30 

×

 0.024 + 2 = 12.7 kg

Value of  

α

Total capacity of connecting indoor units

α

to Model 80

1.0 kg

Models 81 to 160

1.5 kg

Models 161 to 330

2.0 kg

Models 331 or more

2.5 kg

WT03957X01_en

03.3.26, 3:51 PM

8

Summary of Contents for PUHY-P200

Page 1: ...y correcto lea detalladamente este manual de instalaci n antes de montar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente questo manuale di i...

Page 2: ...D 1000 L2 L2 900 E A D A D 1000 1000 900 L2 A A F A 5 B A A Top view B Side view C When there is little space up to an obstruc tion A Front B No restrictions on wall height left and right C Air outle...

Page 3: ...t J Service port A mm Liquid pipe Gas pipe PU H Y P200 12 7 25 4 PU H Y P250 12 7 28 58 PU H Y P315 12 7 31 75 B C D mm Total capacity of indoor units Liquid pipe Gas pipe 80 9 52 15 88 81 160 12 7 19...

Page 4: ...ortar or other incombustible caulking J Incombustible heat insulation material A Power source B Transmission line A Group 1 B Group 3 C Group 5 D Shielded Wire E Sub Remote Controller A Switch Breaker...

Page 5: ...rom being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult...

Page 6: ...igerator oil to deteriorate Use a vacuum pump with a reverse flow check valve The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate Do not use the...

Page 7: ...irmly seated the installation feet may be bent Warning Be sure to install unit in a place strong enough to withstand its weight Any lack of strength may cause unit to fall down resulting in a personal...

Page 8: ...Calculation of Additional Refrigerant Charge Calculate the amount of additional charge based on the length of the piping extension and the size of the refrigerant line Use the table to the right as a...

Page 9: ...port of both the high press pipe and the low press pipe After the vacuum reaches 650 Pa abs continue evacuation for at least one hour or more Never perform air purging using refrigerant Fig 8 3 2 P 3...

Page 10: ...it to CN40 9 Group is set by operating the remote controller 9 2 Control box and connecting position of wiring 1 Connect the indoor unit transmission line to transmission terminal block TB3 or connect...

Page 11: ...ing with the wiring and connections 3 The wire size is the minimum value for metal conduit wiring The power cord size should be 1 rank thicker consideration of voltage drops Make sure the power supply...

Page 12: ...speed operation for 5 minutes after SW ON or until piping temperature becomes 35 C low speed operation for 2 minutes thereafter and then set notch is commenced Hot adjust control When the outdoor unit...

Page 13: ...der Au enanlage Abdeckplatte fest anbringen Wenn die Abdeckung der Elektroanschl sse Abdeckplatte nicht sachge m angebracht wurde kann Staub oder Wasser in die Au enanlage ein dringen und Br nde oder...

Page 14: ...zung des Kurbelgeh uses im Kompressor in Betrieb 1 2 Vorsichtsma nahmen f rVorrichtungen die das K ltemittel R407C verwenden Vorsicht K ltemittel und l Das alte K ltemittel und das K ltemaschinen l in...

Page 15: ...ge berschreitet ist in der folgenden Tabelle die oben gezeigte Dimension h h Wandh he H Ge samth he der Klimaanlage zu der mit markierten Dimension hinzuzuf gen Wenn sich sowohl an der Vorder als auch...

Page 16: ...tzen Sie niemals ein K ltemittel um eine Reinigung der Luft durchzuf h ren Benutzen Sie zum Absaugen immer eine Absaugpumpe 9 Isolieren Sie die Rohrleitung immer einwandfrei Nicht ausreichende Isolati...

Page 17: ...nicht azeotropen K ltemittel R407C usw ein Gasaustritt dazu da sich die Zusammensetzung ndert und die Leistung beeintr chtigt wird Daher den Test auf Luftdichtigkeit mit gr ter Sorgfalt und Vorsicht...

Page 18: ...das K ltemittel verwenden Mit einem Gravimeter Das nach unten bis 0 1 kg messen kann EineVakuumpumpe mit einem Reverse Flow Gegenstrom R ckschlag ventil verwenden F r Modelle R407C Empfohlenes Vakuum...

Page 19: ...Anschlu o am Klemmkasten befestigen 9 3 bertragungskabelanschlu 1 Steuerkabelarten 1 bertragungskabel f r die Verdrahtung bertragungskabelarten Abgeschirmte Kable CVVS CPEVS Kabeldurchmesser Mehr als...

Page 20: ...erungen und Dr hte oder Kupferdr hte mit zu hoher Kapazit t k nnen Betriebsst rungen des Aggregats oder Br nde verursachen Zul ssige Kabell ngen 1 M NET Fernbedienung Gr te L nge ber die Au enaggregat...

Page 21: ...ie Leitungstemperatur 35 C erreicht hat Danach Betrieb mit sehr geringer Laufgeschwindigkeit f r 2 Minuten mit anschlie ender Einstellung des Gebl ses Heizbetriebregelung Wenn die Au enanlage gek hlt...

Page 22: ...ctrocution Lors du d placement et de l installation du climatiseur un endroit diff rent ne le remplissez pas d un r frig rant diff rent utilisez le r frig rant sp cifi sur l appareil Lorsqu un r frig...

Page 23: ...compresseur pendant les interventions techniques Si l appareil est sous tension mais ne fonctionne pas le chauffage du carter la base du compresseur est op rationnel 1 2 Pr cautions prendre avec les d...

Page 24: ...roit o il sera hors de la port e des enfants Un enfant pourrait s touffer en y jouant avec Lors du transport de l appareil ext rieur celui ci doit tre soutenu quatre endroits Si vous le transportez en...

Page 25: ...mais de r frig rant pour purger l air Purgez le toujours l aide d une pompe vide 9 Isolez toujours les tuyaux correctement Une isolation insuffisante risque en effet d entra ner une diminution de la p...

Page 26: ...g Mod les 161 330 2 0 kg Mod les 331 ou plus 2 5 kg 8 2 Pr cautions prendre lors du raccor dement des tuyaux du fonctionnement de la valve Raccorder correctement les conduits et v rifier le bon foncti...

Page 27: ...e ce cylindre n a pas de siphon mettez le cylindre l envers pour transvaser le r frig rant liquide comme l indique le croquis ci dessous Si le cylindre a un siphon comme le montre le croquis de droite...

Page 28: ...e OC IC RC Nombre de contr leurs permis Un seizecontr leurspourunappareilext rieur OC Maximum 2 par groupe Exemple de syst me de fonctionnement reli la terre avec plusieurs appareils ext rieurs Il est...

Page 29: ...onction ner alors que l appareil s est arr t 1 Utiliser une alimentation s par e pour l appareil ext rieur et pour l appareil int rieur 2 Tenir compte des conditions climatiques temp rature ambiante r...

Page 30: ...ada Si el aire acondicionado se instala en una habitaci n peque a deber n tomarse medidas para prevenir que la concentraci n de refrigerante ex ceda los l mites de seguridad incluso si hubiese fugas C...

Page 31: ...al del compresor est en funcionamiento Guarde las tuber as que va a utilizar durante la instalaci n interior con los dos extremos sellados hasta justo antes de la soldadura Guarde los codos y las dem...

Page 32: ...n de la unidad 6 1 Instalaci n Fig 6 1 1 P 2 A Perno de anclaje M10 adquirido en el emplazamiento B No est asentada la esquina Fije la unidad firmemente con pernos para que la misma no se caiga en el...

Page 33: ...de cloro en los refrigerantes y en el aceite del refrigerador convencionales que puede haber en los tubos existentes deteriorar an el nuevo refrigerante Almacene los tubos que vaya a utilizar en la in...

Page 34: ...n el ngulo que muestra la tabla anterior Precauci n Saque siempre el tubo de conexi n de la v lvula de bola y su ldela fuera de la unidad Si se suelda el tubo de conexi n instalado el calor da ar la v...

Page 35: ...Material de calafateado E Banda F Capa estanca G Manguito con borde H Material de encofrado I Mortero u otro encofrado incombustible J Material termoaislante incombustible Cuando se rellene un espacio...

Page 36: ...bles de transmisi n Cable blindado CVVS o CPEVS Di metro del cable M s de 1 25 mm2 Longitud m xima del cable Entre unos 200 m 2 Ejemplos de cables Nombre de los controladores s mbolo y n mero de contr...

Page 37: ...tica funciona sola La configuraci n del ventilador cambia du rante la calefacci n El ventilador se detiene durante el funciona miento de la calefacci n El ventilador no se para una vez detenido el fun...

Page 38: ...ale pannello non installato correttamen te pu consentire l entrata di polvere o acqua con un conseguente rischio di scosse elettriche o incendio In caso di installazione o di spostamento del condizion...

Page 39: ...il riscaldatore del carter sulla base del compressore comunque in funzione 1 2 Precauzioni per le unit che usano il refrigerante R407C Cautela Non usare l esistente tubazione del refrigerante Il vecc...

Page 40: ...nude Rimuovere ed eliminare tutti i sacchetti di plastica in modo che i bambini non li usino per giocare I giochi con i sacchetti di plastica sono infatti molto pericolosi in quanto i bambini corrono...

Page 41: ...l refrigerante accertarsi che la val vola a sfera della sezione esterna sia completamente chiusa impostazione di fabbrica Attivare l unit soltanto se stata completata la tubazione del refri gerante de...

Page 42: ...re la prova con la valvola di arresto della sezione esterna chiusa ed applicare pressione sulla tubazione di collegamento e la sezione interna dal l apertura di servizio della valvola di arresto della...

Page 43: ...OBINAIR 14830 A Manometro del vuoto con termistore Usare anche un manometro del vuoto capace di ottenere 0 5 Torr dopo un funzionamento di cinque minuti 3 Carica del refrigerante Poich il refrigerante...

Page 44: ...missione e della ricezione dei segnali 7 Solamente la linea di trasmissione possedente le specifiche indicate pu es sere collegata al blocco terminale per il comando della sezione esterna Linea di tra...

Page 45: ...per sovracorrente Occorre notare che la sovracorrente generata pu includere una certa quantit di corrente diretta Cautela Alcune installazioni richiedono l adozione di un interruttore per dispersione...

Page 46: ...fase riscaldamento Funzionamento a velocit ultralenta durante 5 minuti dopo attivazione di SW o fino a quando la temperatura della tubazione non raggiunger i 35 C poi funzio namento a bassa velocit p...

Page 47: ...et buitenapparaat moet stevig zijn bevestigd Als de afdekplaat onjuist is bevestigd kan er stof en vocht binnendringen hetgeen elektrische schokken of brand kan veroorzaken Wanneer u de airconditioner...

Page 48: ...storingen ontstaan Raak nooit het oppervlak van de compressor aan terwijl het apparaat aan staat Als het apparaat op de voeding is aangesloten maar niet draait is de carter verwarming geactiveerd 1 2...

Page 49: ...en kinderen stikken in een plastic verpakkingszak die niet verscheurd is Ondersteun bij verplaatsingen het buitenapparaat op vier punten Ondersteuning op drie punten geeft instabiliteit en kan vallen...

Page 50: ...pen aan op het buitenapparaat terwijl het regent Waarschuwing Wanneer u de airconditioner op een andere plaats installeert dient u deze alleen te vullen met die koelstof welke vermeld staat op het app...

Page 51: ...e aansluitpijp aan de gaskant wordt v r verzending in de fabriek gemon teerd 1 Als u de verbindingspijp met flens hard wilt solderen verwijdert u de verbindingspijp met flens van de kogelklep en solde...

Page 52: ...ntiel vulslang en andere onderdelen voor de koel stof te gebruiken die staat aangegeven op het apparaat Gebruik een gravimeter Een exemplaar dat kan meten tot 0 1 kg Gebruik een vacu mpomp met een kee...

Page 53: ...smissiekabels Fig 9 3 1 M NET afstandbediening P 4 Fig 9 3 2 MA afstandbediening P 4 A Groep 1 B Groep 3 C Groep 5 D Afschermdraad E Subafstandsbedieningseenheid Adres Apparaat Bereik Instellingsmetho...

Page 54: ...ten en binnenapparaat gescheiden stroomvoorzieningen 2 Houd bij het aanbrengen van bedrading en verbindingen rekening met de plaatselijke omstandigheden plaatselijke temperatuur direct zonlicht regenw...

Page 55: ...n bij verwarming Ultralage snelheid gedurende 5 minuten nadat SW op AAN staat of totdat pijp temperatuur 35 C wordt daarna bediening op lage snelheid gedurende 2 minu ten en dan treedt de ingestelde w...

Page 56: ...o al m de se arriscar a danificar a unidade Se instalar o ar condicionado num compartimento pequeno dever tirar medidas por forma a evitar que a concentra o do refrigerante exceda o limite de seguran...

Page 57: ...er utilizada durante a instala o ao abrigo das intem p ries e com ambas as extremidades tapadas at ao momento de serem soldadas Guarde os cotovelos e outras juntas num saco de pl stico Se entrar poeir...

Page 58: ...sprotegidas nas alhetas de comuta o de calor do radiador Caso contr rio pode cortar as m os Rasgue o saco de pl stico da embalagem e elimine o para que as crian as n o brinquem com ele podendo sufocar...

Page 59: ...frigerante poder dete riorar o leo refrigerante Se misturar gua poder deteriorar o leo refrigerante Uma vez que o R407C n o cont m cloro os detectores de fugas de g s dos refrigerantes convencionais n...

Page 60: ...e servi o Utilize a para evacua o da tubagem de refrigerante e acrescente carga adicio nal no local Abra e feche a porta com uma dupla chave de bocas Reinstale sempre a tampa no fim da opera o Bin rio...

Page 61: ...a Interior Fita de vinilo Exposto no solo Pano de c nhamo prova de gua Asfal to de bronze Exterior Pano de c nhamo prova de gua Chapa de zinco Tinta a leo Nota Quando utilizar um revestimento de polie...

Page 62: ...emoto M NET P 4 Fig 9 3 2 Controlo Remoto MA P 4 A Grupo 1 B Grupo 3 C Grupo 5 D Fio blindado E Controlo remoto subordinado Endere o Como instalar a cablagem defini o de endere os a Utilize fios blind...

Page 63: ...e a de utilizar o tipo apropriado de interruptor de protec o de sobretens o Note que a sobretens o gerada pode incluir uma certa quantidade de corrente cont nua Cuidado Alguns locais de instala o pode...

Page 64: ...baixa durante 5 minutos depois de ligado o SW ou at a temperatura da tubagem atingir 35 C em funcionamento e depois a baixa velocidade durante 2 minutos em seguida regule o encaixe que iniciou Contro...

Page 65: ...1 1 1 s s Mitsubishi Electric itsubishi Electric 1 65 1 1 65 1 2 R407C 66 1 3 66 1 4 66 1 5 66 2 67 3 67 4 67 5 67 6 68 6 1 68 7 68 7 1 68 7 2 69 8 69 8 1 69 8 2 69 8 3 70 8 4 71 9 71 9 1 71 9 2 71 9...

Page 66: ...66 GB D F I NL E P GR RU TR 80 1 4 L L1 L2 L3 4103 L 20 kg PP PP 1 5 12 1 2 R407C R407C R22 R407C R407C R407C R407C 1 3...

Page 67: ...L1 L2 mm L1 L2 450 250 h 100 mm L1 450 100 550 mm 5 h h 1000 mm 5 Fig 5 0 1 P 2 20 kg 3 2 M E PU H Y P200 PU H Y P250 PU H Y P315 56 dB A 57 dB A 60 dB A PU H Y P200 P250 225 kg PU H Y P315 240 kg 2 9...

Page 68: ...68 GB D F I NL E P GR RU TR 6 6 1 Fig 6 1 1 P 2 A 10 B 100 mm 7 7 1 1 2 3 4 5 6 City Multi Y Series 7 8 9 0 A B R407C R407C...

Page 69: ...D 25 N m E F 25 N m G A 14 N m H 55 N m I 12 7 1 40 A 12 7 40 m a 6 35 10 m 2 100 B 12 7 10 m b 9 52 5 m 3 40 C 12 7 15 m c 6 35 10 m 4 32 D 12 7 10 m d 6 35 10 m 5 63 e 9 52 10 m 12 7 A B C D 40 10 1...

Page 70: ...12 7 50 57 5 15 88 75 80 19 05 100 140 T mm 6 35 9 52 60 90 12 7 15 88 30 60 19 05 20 35 Fig 8 2 3 P 3 8 3 1 Fig 8 3 1 P 3 A B C D L E i F G H I J R22 2 K 650 Pa abs Fig 8 3 2 P 3 A B L C D E F G H I...

Page 71: ...8 3 3 P 3 A 8 4 Fig 8 4 1 P 4 A B C D E A Fig 8 4 2 P 4 A B C D E Fig 8 4 3 P 4 Fig 8 4 4 P 4 A B C D E F A B C D E F G H I J 9 9 1 1 2 5 cm 3 4 5 6 2 7 3 7 8 2 CN41 CN40 9 9 2 1 3 7 h S S 7 C 41 C 4...

Page 72: ...150 MA R C h RC 1 M NET L1 L2 L3 L4 L1 L2 L3 L5 L1 L2 L6 L7 500 m 1 25 mm2 L1 L3 L4 L3 L5 L6 L2 L6 L7 200 m 1 25 mm2 r1 r2 r3 r4 10 m 0 3 1 25 mm2 10 m 1 25 mm2 L8 2 T L1 L2 L3 L4 L1 L2 L6 L7 500 m 1...

Page 73: ...73 GB D F I NL E P GR RU TR 10 10 1 1 2 3 10 4 5 245 C57 W 6 3 mm Cooling heating 1 FF 1 5 SW 35 2 35 SW...

Page 74: ...GR RU TR 1 1 1 s s Mitsubishi Electric 1 74 1 1 74 1 2 R407C 75 1 3 75 1 4 _ 75 1 5 75 2 76 3 76 4 76 5 76 6 76 6 1 76 7 77 7 1 77 7 2 77 8 78 8 1 78 8 2 78 8 3 79 8 4 79 9 80 9 1 80 9 2 80 9 3 80 9...

Page 75: ...75 GB D F I NL E P GR RU TR 1 4 L L1 L2 L3 4103 L N 20 1 5 12 1 2 R407C R407 R22 R407C R407 R407 R407 1 3 80...

Page 76: ...L2 450 250 h 100 L1 450 100 550 5 h h 1000 5 Fig 5 0 1 P 2 20 kg 6 6 1 Fig 6 1 1 P 2 A M10 B 2 M PU H Y P200 PU H Y P250 PU H Y P315 56 dB A 57 dB A 60 dB A PU H Y P200 P250 225 kg PU H Y P315 240 kg...

Page 77: ...77 GB D F I NL E P GR RU TR 7 7 1 1 2 3 4 5 6 CM Series Y 7 8 9 0 A B R407 7 2 Fig 7 2 1 P 3 4 7 10 A B C D 28 58 mm PU H Y P200 34 93 mm PU H Y P315 100...

Page 78: ...kg 80 1 0 81 160 1 5 161 330 2 0 Mo 331 2 5 Fig 8 2 2 P 3 A B A B 90 C 1991 NF D 25 N m E F 25 N m G 14 N m H 55 N m I 12 7 J 25 4 PU H Y P200 28 58 PU H Y P250 31 75 PU H Y P315 K L M N m 6 35 14 18...

Page 79: ...2 94 M 2 3 2 1 0 2 M 2 94 M a 2 R407C 3 8 3 1 2 650 a abs Fig 8 3 2 P 3 A B C D E F G H I J K L M 0 1 R407C 14830 0 5 3 Fig 8 3 3 P 3 A 8 4 Fig 8 4 1 P 4 A B C D E Fig 8 4 2 P 4 A B C D E Fig 8 4 3 P...

Page 80: ...S 7 e CN41 CN40 Fig 9 3 1 M NET P 4 Fig 9 3 2 MA P 4 A 1 B 3 C 5 D E 9 Fig 8 4 4 P 4 A B C D E F 9 1 1 C 2 5 3 4 5 6 2 7 3 7 8 2 CN41 CN40 9 9 2 1 3 7 S TB7 S CN41 CN40 S 7 Fig 9 2 1 P 4 A B 2 27 3 PG...

Page 81: ...40 16 4 0 4 0 6 0 1 5 4 0 4 0 6 0 1 5 M 2 M 200 250 315 1 2 3 1 10 4 5 245 IEC57 YZW 6 3 mm 1 5 NFB f S 7 CN40 g 100 50 h RC 1 M NET L1 L2 L3 L4 L1 L2 L3 L5 L1 L2 L6 L7 500 1 25 2 L1 L3 L4 L3 L5 L6 L...

Page 82: ...82 GB D F I NL E P GR RU TR 10 10 1 1 1 5 35 2 35...

Page 83: ...ksa so utucu ka a olmas halinde bile odadaki so utucu yo unlu unun g venlik s n r n a mas n nlemek zere nlem al nmal d r Ge erli yo unlu un a lmas n nlemeye y nelik nlemler konusunda yetkili sat c n z...

Page 84: ...kan kar t r l rsa R22 vs so utkandaki klor so utucu ya n n bozulmas na sebep olabilir Ters ak nt kontrol vanas olan bir vakum pompas kullan n Vakum pompas ya so utucu devresine geri girebilir ve so ut...

Page 85: ...a g re vibrasyon montaj b l m ne ula abilir g r lt ve vibrasyon duvarlardan ve yer taban ndan kabilir Dolay s yla yeterli b y kl kte vibrasyon kesiciler sa lay n z Yast k tamponlar yast k g vdeler vb...

Page 86: ...kleri Fig 7 2 1 P 3 S v borusu Gaz borusu nitelerin toplam kapasitesi Model numaras lerdeki nite Model Toplam ube Kiti Modeli 4 ubeli Ba 7 ubeli Ba 10 ubeli ba A D nite B lk ube C nite D Tapa PU H Y P...

Page 87: ...u G Servis deli i H 3 yollu conta I Vana J Vana K Silindiri L Terazi M Vakum emme pompas Not Uygun miktarda so utucu eklemeye dikkat edin Ayr ca her zaman sistemi s v so utucuyla contalay n So utucunu...

Page 88: ...40 ile de i tirildi i durumda merkezi kontrol sisteminin terminal blo unun TB7 blendajl terminali S topra a ba lanmal d r Fig 9 2 1 P 4 A G kayna B letim hatt 2 Kablo borusu montaj levhalar 27 sa lanm...

Page 89: ...leri 30 A 100 mA 0 1 san veya daha az 30 A 100 mA 0 1 san veya daha az 40 A 100 mA 0 1 san veya daha az 20 A 30 mA 0 1 san veya daha az 30 A 30 A 40 A 20 A 25 32 40 16 25 32 40 16 4 0 4 0 6 0 1 5 4 0...

Page 90: ...ru s cakl 35 C ye d nceye kadar 5 dakika s reyle son derece d k h zla al r sonra son derece d k h zla al ma 2 dakika daha devam eder Bundan sonra da belirlenen ayarda al r S cakl k ayar kontrol D nite...

Page 91: ...KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK VP SK KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK VP SKNK KKKKKKKKKKKKKKKKKKKKKKKKKKKKKK...

Page 92: ...9 J 0123 012345 01 J UM B 01 NKQK J 01234 i iNI iOI iP QNMP i k J 01 J 0123 J J J 0 1 234 PK OK 1 N 2 QM N 3 PP N 4 OT N 5 jQ S 6 N 7 OP PR N L mrEeFvJmOMM mrEeFvJmORM mrEeFvJmPNR RS _ Y RT _ Y SM _ Y...

Page 93: ...012345 6 0 123 0123456 012345 67 89 8 TKNK 1 01 23 0 123 43L 2 0123 45678 9 3 01 4 5 01 23453678 0123 6 j oO 01234 56 7 8 9 L 0 012345 6789 0 12345 A B 01234 J 0123456789 J 01234567 RK xc KRKMKNz mKO...

Page 94: ...345 0 1 234 5 678 J 0 1234567 J TKOK xc KTKOKNz mKP Q T NM A B C D OUKRU mrEeFvJmOMM PQKVP mrEeFvJmPNR xc KUKOKNz mKP 0 012 34 5 6789 0123456789 01234 xc KUKOKOz mKP Y x z Y_ x z A 0123 456784 B VM C...

Page 95: ...123 4567 MKN oQMT ol_fk fo NQUPM R MKRq 3 0123456 012345 012 01 xc KUKPKPz mKP Y A xc KUKOKPz mKP 01 2 01 01 J 0 1 23456789 0 123456789 J 01 UKPK 1 01 2 0134 xc KUKPKNz mKP A B C D i E e F G H I J oOO...

Page 96: ...KQ xc KVKPKOz j mKQ A N B P C R D E 0 1 23 01230456378 q_T p kQN kQM q_T p xc KVKOKNz mKQ A B OK OT 0 PK md VKPK 1 NK ssp mbsp NKOR O OMM 2 OK MKP NKOR O NM N VK l f o N NS l K l f l Jl f Jf K N jN O...

Page 97: ...OR O jJk W iN iPHiQ iS iOHiS iT OMM NKOR O W cNHcO cNHcOHcPHcQ OMM MKP NKOR O VKQK xc KVKQKNz mKQ A B C D E L NK OK PK NM QK RK 0123456789 fb OQR RT vwt SK P 0123 456 7 01234 0 1 W 012 34 5678 0123456...

Page 98: ......

Page 99: ......

Page 100: ...the contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Comp...

Reviews: