- 70 -
<Abnormality detected during unit operation: Indoor unit>
Abnormal-
ity display
P6
Meaning of abnormality display and
abnormality troubleshooting
Freezing/excessive rise protection
operation
1) Freezing protection
When the piping temperature re-
mains at –15
°
C or lower for 3 min-
utes after 3 minutes have elapsed
since the compressor started, the
compressor enters the 6 minutes
restart prohibit mode and if the
piping temperature again remains
at –15
°
C for 3 minutes within 16
minutes after 6 minutes restarting,
an abnormality is recognized.
2) Excessive rise protection
When a piping temperature rise
to 70
°
C or higher is detected af-
ter the compressor starts, the
compressor enters the 6 minutes
restart prohibit mode. If a piping
temperature rise up to 70
°
C or
higher is detected again within 10
minutes after 6 minutes restarting,
an abnormality is recognized.
Cause
<Cool and dry>
1
Filter is clogged (insufficient air flow).
2
Air duct short cycle.
3
Low load operation (low temperature)
exceeding allowable range.
4
Indoor fan motor faulty.
5
Outdoor fan control faulty (intermedi-
ate period, winter).
6
Refrigerant overcharged.
7
Refrigerant circuit faulty (clogged).
<Heat>
1
Filter clogged (insufficient air flow)
2
Air duct short cycle.
3
Overload operation (high temperature)
exceeding allowable range.
4
Indoor fan motor faulty.
5
Outdoor fan control faulty (intermedi-
ate period)
6
Refrigerant overcharged.
7
Refrigerant circuit faulty (clogged)
8
Outdoor unit bypass circuit faulty.
Judgment method and remedy
<Cool and dry>
1
Check filter for clogging.
2
Remove obstruction.
4
Check fan motor operation and winding
resistance.
5
Check outdoor fan motor operation.
6 7
Check refrigerant circuit operation.
<Heat>
1
Check filter for clogging.
2
Remove obstruction.
4
Check fan motor operation and winding
resistance.
5
Check outdoor fan motor operation.
6
-
8
Check refrigerant circuit operation.