-3.
Fixing hanging bolts
1
1
1
1
1
-3.1. Fixing hanging bolts
(Use M10 hanging bolts. The bolts should be supplied in the field.)
(Give site of suspension strong structure.)
Hanging structure
•
Ceiling: The ceiling structure varies from one building to one another. For de-
tailed information, consult your construction company.
1
Reinforcing the ceiling with additional members (edge beam, etc) must be re-
quired to keep the ceiling at level and to prevent the ceiling from vibrations.
2
Cut and remove the ceiling members.
3
Reinforce the ceiling members, and add other members for fixing the ceiling
boards.
For wooden construction
•
Use the tie beam (for one story building) or second-floor beam (for two story
building) as strength members.
•
To hang the air-conditioner, use a hard square timber of more than 6 cm if the
distance between beams is less than 90 cm and a hard square timber of more
than 9 cm if the distance between beams is less than 180 cm.
For reinforced concrete construction
•
As shown in the figure below, fix the hanging bolts, or use square timbers to fix
the hanging bolts.
A
B
D
C
E
E
A
Ceiling board
B
Edge beam
C
Tie beam
D
Square timber for hanging the
air conditioner
E
Pitch
[Fig.
1
1
1
1
1
-3.1.1]
Product Weight (kg)
PEH-7MYB
67 kg
PEH-8MYB
70 kg
PEH-10MYB
84 kg
F
G
H
F
Insert: 100 to 150 kg (1 piece)
(field supply)
G
M10 hanging bolt (field supply)
H
Reinforcement
[Fig.
1
1
1
1
1
-3.1.2]
1
1
1
1
1
-4.
Installing the unit
1
1
1
1
1
-4.1. Hanging the unit body
s
Bring the indoor unit to an installation site as it is packed.
s
To hang the indoor unit, use a lifting machine to lift and pass through the
hanging bolts.
s
Install the indoor unit before ceiling work.
<When installing the suspension fixture prior to installation of the indoor unit>
1. Loosen each suspension fixture bolt slightly, and remove the fixture and U-
shaped washers.
2. Adjust each suspension fixture bolt.
3. Attach a washer, nut and suspension fixture to each suspension bolt. (The
washers and nuts are to be supplied locally.)
4. Hook the indoor unit to the suspension fixtures.
5. Make sure that the unit is positioned level, then tighten each nut.
A
B
[Fig.
1
1
1
1
1
-4.1.1]
A
Unit body
B
Lifting machine
* Two installation methods are available
<When hanging the indoor unit directly>
1. Attach a washer and nut(s) to each suspension bolt. (The washers and nuts
are to be supplied locally.)
2. Fit the indoor unit to each suspension bolt.
3. Make sure that the unit is positioned level, then tighten each nut.
A
B
A
A
30
B
*1
[Fig.
1
1
1
1
1
-4.1.2]
A
Nut
B
Washer
A
B
When using inlet duct
100 or more
130 or more
When not using inlet duct
0 or more
30 or more
Nut (*1) is not required if distance A is 0.
A
B
When using inlet duct
100 or more
130 or more
When not using inlet duct
25 or more
55 or more
A
A
30
B
10
[Fig.
1
1
1
1
1
-4.1.3]
A
Be sure to attach a U-shaped washer (4 washers in total).