Easy Dehumidifier
(a) Modifies humidity setting or operates CIRCULATE mode (blower only mode) according to the room temperature.
(b) Switches temperature table every 60 seconds to prevent the blower from turning on and off at the 3-minute restart for the coloured
section in the chart below. (51% – 59%)
(c) When the room temperature is above 29
°
C (temperature rising) or 27
°
C (temperature decreasing), CIRCULATE mode operates with the
humidity below 50%. The unit activates the dehumidifier when the humidity rises above 60%, and returns to CIRCULATE mode when
the humidity drops below 50%.
0
60%
ON
ON
OFF
OFF
OFF
OFF
ON
ON
60%
60%
50%
50%
50%
1
2
3
Current humidity
– Set humidity
20
°
C
27
°
C
34
°
C
+3%
–1%
+5%
+1%
Temperature
Temperature table
Set humidity
Fan rank
Compressor
Fan rank
Compressor
Fan rank
Compressor
22
°
C
29
°
C
36
°
C
Rank 1
Rank 1
ON
ON
Stop
Rank 1
Rank 1
Rank 2
Rank 2
ON
ON
Stop
Circulate
To
Dehumidifier
mode
To
Dehumidifier
mode
Rank 4
Rank 5
To
Circulate
mode
Rank 5
Rank 5
To
Circulate
mode
Dehumidifier mode
Circulate
Dehumidifier mode
Circulate
set humidity 60%
Dehumidifier mode
set humidity 50%
Circulate
set humidity 60%
Set humidity 60%
Set humidity 50%
ON
OFF
ON
OFF
50%
60%
Humidity
Compressor
Blower
~20
°
C~
~27
°
C~
Temperature
E16S
E16SX