8.3 Writing Data to Specified File
8-17
8
QCPU
INS
T
R
UCTIONS
SP
_FWRITE
SP_FWRITE
Operation Error
In any of the following cases, an operation error occurs, the error flag (SM0) is turned ON, and
the corresponding error code is stored to SD0.
• Drive specified for drive specification device
contains the medium other than the ATA
card.
(Error code: 4100)
• Values specified for control data and the following devices are out of the setting range.
(Error code: 4100)
• Value specified for "number of request write data"
is out of the setting range, or
exceeds the device range specified for
+1 and the following devices.
(Error code: 4101)
• Empty space in the ATA card is insufficient.
(Error code: 4100)
• No free space is found when an attempt is made to create a new file. (Error code: 4100)
• Invalid device is specified.
(Error code: 4004)
• Access error occurred in the ATA card.
(Error code: 4100)
• An unusable value is set for a file name (
).
(Error code: 4100)
• The attribute of a file name (
) is "read only".
(Error code: 4100)
• The device specified for
or
exceeds the corresponding device range. (For Universal
model QCPU only)
(Error code: 4101)
s0
d0
s2
s2
s1
s1
d0
d1
Summary of Contents for MELSEC Q Series
Page 1: ...Structured Programming Manual Mitsubishi Programmable Controller QCPU Common Instructions ...
Page 2: ......
Page 14: ...A 12 MEMO ...
Page 340: ...6 178 MEMO MTR ...
Page 708: ...7 368 MEMO ...
Page 776: ...8 68 MEMO ...
Page 796: ...9 20 MEMO ...
Page 804: ...App 8 MEMO ...
Page 812: ...Index 8 MEMO ...
Page 815: ......