5.3 Output Instructions
5.3.10 Pulse conversion of direct output
5-43
5
SE
Q
U
EN
C
E
INSTRUCTION
S
DE
LT
A
DELTA
(2) The DELTAP instruction is used by commands for rising pulse execution for an intelligent
function module.
O
p
erat
i
on
E
rror
In the following case, an operation error occurs, the error flag (SM0) is turned ON, and the
corresponding error code is stored to SD0.
• A direct access output number specified for
has exceeded the CPU module output
range.
(Error code: 4101)
Program
E
xam
pl
e
In the following program, CH1 of the AD61 module mounted at slot 0 of the main base unit is
preset, when X20 turns ON.
[Structured ladder]
[ST]
IF X20 THEN
MOVP(TRUE,K0,U0¥G1);
MOVP(TRUE,K0,U0¥G2);
DELTAP(TRUE,DY11);
END_IF;