FX2N Series Programmable Controllers
Standards
ix
Note Concerning the CE Marking
This document does not guarantee that a mechanical system including this product will comply with the following
standards. Compliance to EMC directive and LVD directive of the entire mechanical system should be checked by the user
/ manufacturer. For more details please contact the local Mitsubishi Electric sales site.
Programmable logic controllers are open-type devices that must be installed and used within conductive control boxes.
Please use the FX
2N
Series programmable logic controllers while installed in conductive shielded control boxes.
Please secure the control box lid to the control box (for conduction).
Installation within a control box greatly affects the safety of the system and aids in shielding noise from the programmable
logic controller.
EMC
The following products have shown compliance through direct testing (of the identified standards below) and design
analysis (through the creation of a technical construction file) to the European Directive for Electromagnetic Compatibility
(89/336/EEC) when used as directed by the appropriate documentation.
Refer to a manual or related material of each product other than the following.
Type :
Programmable Controller (Open Type Equipment)
Models :
MELSEC FX
2N
series manufactured
from July 1st, 1997
FX
2N
-
MR-ES/UL
FX
2N
-
MT-ESS/UL
Where
indicates:16,32,48,64,80,128
FX
2N
-
ËË
ER-ES/UL
FX
2N
-
ËË
ET-ESS/UL
Where
ËË
indicates:32,48
FX
2N
-16EX-ES/UL
FX
2N
-16EYR-ES/UL
FX
2N
-16EYT-ESS/UL
FX
2N
-232-BD
FX
2N
-485-BD
FX
2N
-422-BD
FX
2N
-8AV-BD
FX
2N
-CNV-BD
FX
2N
-CNV-IF
from April 1st, 1998
FX
2N
-
MR-DS
FX
2N
-
MT-DSS
Where
indicates:32,48,64,80
FX
2N
-48ER-DS
FX
2N
-48ET-DSS
from August 1st, 1998
FX
2N
-
UU
MR-UA1/UL
Where
UU
indicates:16,32,48,64
FX
2N
-16MR-DS
FX
2N
-16MT-DSS
FX
2N
-48ER-UA1/UL
from July 1st, 2001
FX
2N
-ROM-E1
from August 1st, 2005
FX
2N
-8ER-ES/UL
FX
2N
-8EX-ES/UL
FX
2N
-8EYR-ES/UL
FX
2N
-8EYT-ESS/UL
For the products above, PLCs manufactured
before March 31st, 2002 are compliant with EN50081-2 (EN61000-6-4) and EN50082-2
from April 1st, 2002 to April 30th, 2006 are compliant with EN50081-2 (EN61000-6-4) and EN61131-
2:1994+A11:1996+A12:2000
after May 1st, 2006 are compliant with EN61131-2:2003
Standard
Remark
EN50081-2:1993
Electromagnetic compatibility
EN61000-6-4:2001 - Generic emission standard
Industrial environment
Compliance with all relevant aspects of the standard.
(Radiated Emissions and Mains Terminal Voltage Emissions)
EN50082-2:1995
Electromagnetic compatibility
- Generic immunity standard
Industrial environment
Compliance with all relevant aspects of the standard.
(RF immunity, Fast Transients, ESD, Conducted and Power
magnetic fields)
EN61131-2:1994
Programmable controllers
/A11:1996
- Equipment requirements and tests
/A12:2000
Compliance with all relevant aspects of the standard.
(RF Immunity, Fast Transients, ESD and Damped oscillatory
wave)
EN61131-2:2003
Programmable controllers
- Equipment requirements and tests
Compliance with all relevant aspects of the standard.
(Radiated Emissions, Mains Terminal Voltage Emissions, RF
Immunity, Fast Transients, ESD, Surge, Voltage drops and
interruptions, Conducted and Power magnetic fields)
Summary of Contents for FX2N series
Page 1: ...HARDWARE MANUAL FX2N SERIES PROGRAMMABLE CONTROLLERS ...
Page 38: ...FX2N Series Programmable Controllers Introduction 1 1 18 MEMO ...
Page 78: ...FX2N Series Programmable Controllers Wiring techniques 4 4 18 MEMO ...
Page 88: ...FX2N Series Programmable Controllers Inputs 5 5 10 MEMO ...
Page 132: ...FX2N Series Programmable Controllers Diagnostics 7 7 22 MEMO ...
Page 136: ...FX2N Series Programmable Controllers Appendix A A 4 MEMO ...