-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
Operation 4
4-17
[ Example of I/O assignment in dedicated I/O type unit mode ]
The table below shows I/O assignment for remote I/O units in the system above.
•
Units B and C are units having 4 points dedicated to output. If a unit having 8 points dedicated to output
is connected as Unit C (station No. 3), latter four points will malfunction.
•
Station Nos. for input and station Nos. for output are already determined respectively. Even if the number
of occupied I/O points is not more than the specified number, an inappropriate unit cannot be connected.
For example, if a unit having eight points dedicated to input is connected to the station No. 6 or 7 which is
set for output, it will not function at all.
FX
2N
-16MR
Y030 to 033
Y034 to 037
X030 to
037
16EX
16EYR
Master
unit
X000 to 007
Y000 to 007
X010 to
027
X030 to 047
Y030 to 047
Y010 to
027
T branch
4 output points
(1 station)
Station
No.2
Station
No.3
Station
No.0
B
C
A
Y040 to 047
E
Station
No.6
D
X040 to 047
Station
No.4
I/O occupation setting switch
MOD0: ON
MOD1: OFF
MOD2: OFF Dedicated I/O type unit mode
32 points are occupied.
4 output points
(1 station)
8 output points
(2 stations)
8 output points
(2 stations)
8 output points
(2 stations)
0
1
2
3
4
5
6
7
Station
No.
X
Y
X30
Y30
X40
Y40
A
B
C
D
E
: A bold line frame shows one remote unit.
Summary of Contents for FX2N-16LNK-M
Page 1: ...USER S MANUAL FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK ...
Page 8: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Contents vi MEMO ...
Page 50: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Troubleshooting 5 5 6 Memo ...
Page 58: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Appendix A 6 Memo ...
Page 59: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK ...