Connection and Wiring 3
3-4
Countermeasures against erroneous inputs or outputs
Perform wiring of a PC unit and a stabilized power supply unit from a same power supply.
•
When the 24V DC service power supply of a PC unit is used
FX
0N
/FX
1N
/FX
2N
Series AC power supply type
When the 24V DC service power supply of a basic unit or an extension unit is used, pay attention so that
the capacity of 24V DC power supply built in each unit is not exceeded.
For calculation of the capacity of the service power supply, refer to the handy manual supplied together
with the basic unit.
When an FX
0N
Series PC is connected, running of a master block is instantaneously interrupted approx-
imately 2 sec after the power to the master block is turned on.
It is recommended to read the information on data/RUN terminal of a remote I/O unit 3 sec after the
power is turned on.
•
When a stabilized power supply unit is used
FX
0N
/FX
1N
/FX
2N
Series AC power supply type
Basic or extension unit
L
Master block
Remote I/O unit
N
24+
COM
24+ 24-
24+ 24-
L
N
24+ 24-
24+ 24-
24
+
24
-
Stabilized
power
supply
L
N
Basic or extension unit Master block
Remote I/O unit
Summary of Contents for FX2N-16LNK-M
Page 1: ...USER S MANUAL FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK ...
Page 8: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Contents vi MEMO ...
Page 50: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Troubleshooting 5 5 6 Memo ...
Page 58: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Appendix A 6 Memo ...
Page 59: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK ...