FX
2N
-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
Operation 4
4-5
*1 M8009: Checks status of the 24V DC power supplied from the outside when 24V DC has come down.
*2 The brightness changes in accordance with the number of connected remote I/O units (As the number of
units becomes larger, the LED becomes brighter.)
Terminal block
Connects signals, power supplies and RUN outputs (size: M3, tightening torque: 100
to 135 N
y
cm).
Name
Description
DATA
Data
DG
Data ground
Ground
24+
+24V DC power supply for transmission (plus side)
24-
-24V DC power supply for transmission (minus side)
RUNA
RUNB
External output for lighting (or extinguished) status of RUN LED
ON: RUN LED is lit.OFF: RUN LED is extinguished.
Name
Status
Description
24
+
24
-
DATA
DG
RUNA
RUNB