Connection and Wiring 3
3-2
Cautions on system configuration
Pay attention to the following points in the power supply wiring (system design) so that erroneous inputs to or
outputs from remote I/O units can be prevented.
1 )
Countermeasures against erroneous inputs or outputs occurred when the power is turned on or off
•
When the power is turned on
[Draft 1]Turn on at first the power of remote I/O units and the power of master blocks supplied from the
outside. Then, turn on the power of a basic PC unit.
[Draft 2]Turn on at the same time the power of remote I/O units, the power of master blocks supplied
from the outside and the power of a basic PC unit.
•
When the power is turned off
[Draft 1]Turn off at first the power of a basic PC unit. Then, turn off the power of remote I/O units and the
power of master blocks supplied from the outside.
[Draft 2]Turn off at the same time the power of a basic PC unit , the power of remote I/O units and the
power of master blocks supplied from the outside.
2 )
Countermeasures against erroneous inputs occurred when the power of a remote I/O unit is instanta-
neously interrupted
If the power of a remote I/O unit is instantaneously interrupted, erroneous inputs may occur.
•
Causes of erroneous inputs by instantaneous power interruption
The hardware of a remote I/O unit converts the I/O unit power supply (24V DC) into 5V DC inside, then
uses it.
If the power of a remote I/O unit is instantaneously interrupted, the following relationship is generated.
(Time until 5V DC inside remote I/O unit is turned off)
>
(Response time of input unit ON
→
OFF)
Accordingly, if I/O refresh occurs within the time shown as
➀
in the figure below, erroneous inputs occur.
Summary of Contents for FX2N-16LNK-M
Page 1: ...USER S MANUAL FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK ...
Page 8: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Contents vi MEMO ...
Page 50: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Troubleshooting 5 5 6 Memo ...
Page 58: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Appendix A 6 Memo ...
Page 59: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK ...