-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
Operation 4
4-15
4 )
Assign remote I/O units to be used to the table on the left.
•
In the connection sequence, four points dedicated to input are located in a former place. However, four
points dedicated to input are set to the station No. 4 because the station Nos. 2 and 3 are set for output.
•
The station No. 5 is vacant. However, when one more unit having four points dedicated to input is used, it
can be assigned to the station No. 5.
If a unit having eight points dedicated to input is assigned to the station No. 5, latter four points of this unit
will malfunction.
8 points dedicated
to input
4 points dedicated
to input
8 points dedicated
to output
Example
{ {
{ { { {
{ { { { { {
{ { { { { { { {
X (input)
Y (output)
Station No. 0 Station No. 1 Station No. 2 Station No. 3
8 points dedicated to input
8 points dedicated to output
4 points dedicated to input
Station No. 4 Station No. 5