82
-
Over heat of compressor
Gas shortage, defective discharge
pipe sensor
Is discharge pipe sensor
resistance value good?
(page 80)
Is sufficient quantity of refrigerant
circulated?
Defective outdoor PCB
YES
YES
NO
NO
YES
NO
Check if there are any
places where gas is leaking.
Connector connection check, resistance
value check, replacement of discharge pipe
sensor
Does trouble persist after
charging gas?
Clogged capillary tube or
strainer, defective EEV, etc.
Error of signal transmission
Wiring error including power cable, defective indoor/
outdoor PCB
Does error persist after power
reset?
Are the lines connecting the indoor
and outdoor units connected
normally?
Is DC 0~Approx. 20V detected
between
②
~
③
terminals on
outdoor terminal block?
YES
YES
NO
NO
YES
NO
Trouble by transient cause, not unit trouble.
Correct improper wire connection on indoor/
outdoor unit.
Defective outdoor PCB
YES
YES
NO
NO
Is DC 0~Approx. 20V detected
between
②
~
③
terminals on indoor
terminal block?
Is AC 220/230/240V applied between
①
~
②
on the indoor terminal block?
Defective outdoor PCB. Check crossover wires.
Defective indoor PCB
Check crossover wires.