80
-
(7) Inspection procedures corresponding to detail of trouble
Sensor error
(Short circuit)
(Broken wire)
Is connector connection good?
YES
YES
NO
NO
Replace PCB.
Correct connection.
Replace sensor.
Is sensor resistance value good?
◆
Sensor temperature characteristics (Room
temp., indoor heat exchanger temp., out-
door heat exchanger temp., outdoor air
temp.)
Temperature (˚C)
Resistance
(k
Ω
)
30
25
20
15
10
5
30
20
10
40
50
60
70
0
-10
◆
Discharge pipe sensor temperature characteristics
Indoor fan motor error
Is connector connection good?
YES
NO
NO
Is the output of the indoor PCB
normal?
Normal
NO
YES
YES
Correct connector connection
Is fan motor resistance value good?
Defective indoor PCB
Replace indoor fan motor
Notes (1) See pages 85 for the fan motor and indoor PCB check pro-
cedure.
(2) After making sure the fan motor and indoor PCB are nor-
mal, connect the connectors and confirm that the fan motor
is turning.
(If power is turned on while one or the other is broken
down, it could cause the other to break down also.)
* Disconnect the fan motor
connector, then investigate
the fan motor and indoor
PCB separately.
Broken sensor wire,
connector poor connection
0
0
20
40
60
80
100
120 135
20
40
60
80
100
120
140
160
180
(Short circuit)
(Broken wire)
Temperature (˚C)
Resistance
(k
Ω
)
Defective fan motor, connector poor
connection, defective indoor PCB