95
–
'14 • KX-SM-200
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor unit
Heat source unit
Content
*1 E37-1: 1-time flash (Tho-R1), E37-2: 2-time flash (Tho-R2), E37-5: 5-time flash (Tho-SC), E37-6: 6-time flash (Tho-H)
E37
E37-1, 2, 5, 6*1
Heat source unit heat exchanger
temperature thermistor (Tho-R) and sub-cooling coil
temperature thermistor (Tho-SC,-H) anomaly
Keeps flashing
Stays OFF
Keeps flashing
*1
1. Applicable model
5. Troubleshooting
Heat source unit
Diagnosis
Countermeasure
Is the
connector of
thermistor connected
properly?
Are the
characteristics of
thermistor
OK?*2
*2
Check several times to prove any poor connection
Heat source unit heat exchanger temperature thermistor (Tho-R1-R2)
Subcooling coil thermistor (Tho-SC, Tho-H)
Temperature-resistance characteristics
Save data for 30 minutes before stopping in Mente PC.
YES
NO
NO
YES
Temperature (°C)
5kΩ at 25°C
Temperature thermistor resistance (kΩ)
Check and save the data of
operating conditions.
Check the conditions whether
it occurs immediately after the
power on or during operation
or stopping.
Check the sensed value.
Compare the temperature
on Mente PC with actual
measured value.
Insert the connector
securely.
Replace thermistor.
(Tho-SC, Tho-H, Tho-R)
Replace heat source unit
control PCB.
2. Error detection method
Detection of anomalously low
temperature (resistance)
of Tho-R or Tho-SC or Tho-H.
3. Condition of error displayed
• If -50°C or lower is detected for 5
seconds continuously within 2-minutes to
2-minutes 20-seconds after the compressor
ON, the compressor stops. And after
3-minutes delay, the compressor starts
again automatically, but if this anomalous
temperature is detected 3 times within 40
minutes after the initial detection.
• If -50°C or lower is detected for 5 seconds
continuously within 20 seconds after power ON.
4. Presumable cause
• Broken thermistor harness or
the internal wire of sensing
section (Check the molded
section as well)
• Disconnection of thermistor
harness connection (connector).
• Heat source unit control PCB
anomaly.
Note: