Model
VL-350CZPVU-L-E, VL-350CZPVU-R-E
VL-350CZPVU-L-ERT, VL-350CZPVU-R-ERT
Heat exchange system
Heat recovery ventilating system
Heat exchanger material
Sensible heat exchanger
Cladding
Steel sheet
Heat insulation material
Polyethylene foam
Motor
DC motor
Blower
210 mm diameter centrifugal fan
Filter
Non-woven fabrics filter
Duct connecting
Synthetic resin
Duct connecting cover
Styrene foam
Outside air condition
Shall be higher than -15°C
Return (Suction) air
condition
Shall be lower than 40°C, 95%RH
Surrounding air condition Indoor temperature and humidity should not exceed the dew point temperature 12°C
(e.g. RH 60%, 20°C)
Supply fan operation under
low outdoor temperature
-3°C to -15°C: Intermittent operation
-15°C or less: Supply air fan stopped.
*Exhaust air fan:
continuous operation
Function
Heat exchange ventilation/ By-pass ventilation, Fan speed 1,2,3,4
The air flow increment by 1% from 25% to 100%
Dimensions
(Height x Width x Depth)
623 mm x 658 mm x 432 mm
Weight
32 kg
Electrical power supply
220–240 V 50 Hz/ 220 V 60 Hz
Insulation resistance
10 MΩ or more
Dielectric strength
1000 V AC 1 minute
Maximum current [A]
1.32
Specifications
Ventilation mode
Heat exchange mode
Fan speed
Fan Speed 4 (100%) Fan Speed 3 (70%) Fan Speed 2 (50%) Fan Speed 1 (30%)
Running current
[A]
1.08
0.52
0.31
0.18
Input power
[W]
155
71
37
19
Air volume
[m
3
/h]
320
224
160
96
[L/s]
89
62
44
27
External static
pressure
[Pa]
150
74
38
14
Temperature
exchange efficiency [%]
85
87
88
90
Sound pressure
level at 3 m
[dB]
35
26
19
15 >
Attention
1. The above values are at factory default.
2. The running current, the input power, the efficiency and the noise are based on the rating air volume, and 230 V
50 Hz.
3. The sound pressure level at 3 m is spherical.
4. Temperature exchange efficiency (%) is based on winter conditions.
5. Mitsubishi Electric measures figures in the chart according to EN13141-7:2010, and the characteristic curves are
measured by chamber method.