─ 44 ─
No.
Symptom
Diagnosis method
Corrective action
1 Lossnay operation is
not correct for the ana-
log signal sent from the
external device con-
nected to TM200 on the
signal interface circuit
board.
Check if connection with the external
device is disconnected or loose.
Connect the external device correctly.
Check that terminal block connection is
correct.
Connect the terminals correctly.
(Refer to “5.2 External device connec-
tion use” in the Installation Manual.)
Power (low-voltage output) is not sup-
plied from the externally connected
device.
Check the external device.
* TM200 is a low-voltage input terminal.
(Refer to “5.2 External device connec-
tion use” in the Installation Manual.)
Lossnay setting is incorrect.
Check the controller settings.
(Refer to “6.4.5 External input” of the
Installation Manual.)
2 Lossnay operation is
not correct for the con-
tact signal sent from the
external device con-
nected to TM201 on the
signal interface circuit
board.
Check if connection with the external
device is disconnected or loose.
Connect the external device correctly.
Check that terminal block connection is
correct.
Connect the terminals correctly.
(Refer to “5.2 External device connec-
tion use” in the Installation Manual.)
No signal (volt-free contact signal) is
supplied from the externally connected
device.
Check the external device.
* TM201 is the contact input terminal.
(Refer to “5.2 External device connec-
tion use” in the Installation Manual.)
Lossnay setting is incorrect.
Check the controller settings.
(Refer to “6.4.5 External input” of the
Installation Manual.)
3 Lossnay operation is
not correct for the sig-
nal sent from the air
conditioner (Mr. Slim)
connected to TM2 on
the control circuit board.
Check if connection with the air condi-
tioner is disconnected or loose.
Connect the air conditioner (Mr. Slim)
correctly.
Check that terminal block connection is
correct.
Connect the terminals correctly.
(Refer to “5.2 External device connec-
tion use” in the Installation Manual.)
The air conditioner (Mr. Slim) setting is
incorrect.
Check the setting of the air conditioner
(Mr. Slim).
4 External device opera-
tion is not correct for
the signal sent to the
external device con-
nected to TM3 on the
control circuit board.
Check if connection with the external
device is disconnected or loose.
Connect the external device correctly.
Check that terminal block connection is
correct.
Connect the terminals correctly.
(Refer to “5.2 External device connec-
tion use” in the Installation Manual.)
Check if the externally connected
device is faulty.
Check the external device.
Lossnay setting is incorrect.
Check the controller setting.
(Refer to the functions No. 57, 58, 81 in
“8. (2) Function setting list” (page 25
and 26).)
5 The externally installed
controller connected
to TM4 on the control
circuit board cannot be
turned on.
Check if connection with the externally
installed controller is disconnected or
loose.
Connect the controller correctly.
Check that terminal block connection is
correct.
Connect the terminals correctly.
(Refer to “5.2 External device connec-
tion use” in the Installation Manual.)
Check if the cable between the
Lossnay unit and controller is
disconnected.
Connect the cable and connector cor-
rectly.
(Refer to the Installation Manual of
P-RCC-E.)
[2] Diagnosis of an externally connected device