27
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Outdoor unit
precharged
900
800
1,050
14m
270
270
7m
0
0
6m
0
0
5m
0
0
11m
180
180
Models
Refrigerant piping length (one way)
Calculation : Xg=30g/m
%
(Refrigerant piping length(m) - 5)
8m
90
90
9m
120
120
10m
150
150
12m
210
210
13m
240
240
15m
300
300
20m
450
450
SUZ-KA25VA.TH
SUZ-KA25VAH.TH
SUZ-KA35VA.TH
SUZ-KA35VAH.TH
SUZ-KA35VAR1.TH
SUZ-KA35VAHR1.TH
SUZ-KA25VAR1.TH
SUZ-KA25VAHR1.TH
Refrigerant Piping
Max. length
A
+
Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
+
Max. Height
difference
12m
Indoor
unit
(SLZ/SEZ)
Outdoor unit
MAX. HEIGHT DIFFERENCE
Refrigerant piping
Max. length: m
A
20
Gas
9.52
Liquid
6.35
Piping size O.D: mm
Models
SUZ-KA25VA.TH
SUZ-KA35VA.TH
SUZ-KA25VAH.TH
SUZ-KA35VAH.TH
SUZ-KA25VAR1.TH
SUZ-KA35VAR1.TH
SUZ-KA25VAHR1.TH
SUZ-KA35VAHR1.TH
SUZ-KA25VA.TH SUZ-KA25VAH.TH SUZ-KA25VAR1.TH SUZ-KA25VAHR1.TH
SUZ-KA35VA.TH SUZ-KA35VAH.TH SUZ-KA35VAR1.TH SUZ-KA35VAHR1.TH
MAX. REFRIGERANT PIPING LENGTH