87
[SUZ-KA50/60/71VA
(1)
.TH SUZ-KA60VAR2.TH]
X
Check of HPS
Infinity
0
Yes
No
1. Disconnect the connector CN681 in the electronic control P.C. board.
2. Check the resistance of HPS after 1 minutes have passed since the outdoor unit power supply was turned off.
Check the resistance between
each terminal.
Reconnect CN681.
Turn on power supply to the indoor and outdoor unit.
3 minutes later, starts EMERGENCY OPERATION.
Is HPS protection displayed
immediately after compressor
starts?
Replace HPS.
Replace the electronic control P.C. board.
Normal
When the operation frequency does not go up from lowest frequency.
SUZ-KA60VAR2.TH
SUZ-KA71VA
(1)
.TH
Outdoor unit does not operate at all, or stops immediately due to overcurrent.
Check of current-limiting resistor
Y
Turn ON the power
supply and press
EMERGENCY
OPERATION switch.
Replace the outdoor
electronic control P.C.
board or power P.C.board
or the compressor.
Replace the noise filter P.C.
board or the outdoor
electronic control P.C.
board.
Does the rush current
limiting relay(X64) work
properly?
Open
Not
open
No
No
Yes
Yes
Is the resistance of current-limiting
resistor (R64A or R64B) on the
noise filter P.C. board normal?
(Normal resistance : 5
$
5%)
Replace the noise filter P.C.board.
Replace the power P.C. board.
Does LED on the outdoor
electronic control P.C. board
light up?
When the current-limiting resistor is open, the rush current limiting relay (X64) may not work properly.