89
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
e Check of compressor winding
Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between
the compressor terminals.
<<Measurement point>>
at 3 points
BLK-WHT
BLK-RED
WHT-RED
<<Judgement>>
Refer to 12-4.
0 [
Ω
] ················Abnormal [short]
Infinite [
Ω
] ·······Abnormal [open]
NOTE
: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
f Check of compressor operation time
Compressor starts
Abnormal
(IPM failure)
(Compressor winding short)
Abnormal
(Compressor lock out)
(Starting defect)
Abnormal
(Poor contact,)
(Outdoor P.C. board defect)
(Disconnected connector)
Abnormal
(Refrigerant circuit defect)
(Closed valve)
Normal
0 second
1 second
2 seconds
10 seconds
10 minutes
<<Judgement>>
Thermistor
Symbol
Connector, Pin No.
Board
Defrost
RT61
Between CN641 pin1 and pin2
Inverter P.C. board
Discharge temperature
RT62
Between CN641 pin3 and pin4
Fin temperature
RT64
Between CN642 pin1 and pin2
Ambient temperature
RT65
Between CN643 pin1 and pin2
Outdoor heat exchanger temperature
RT68
Between CN644 pin1 and pin3
Replace the thermistor except RT64.
When RT64 is abnormal, replace the inverter P.C.
board or the outdoor power board.
Replace the inverter P.C. board
or the outdoor power board.
No
No
Is the thermistor normal?
(Refer to 12-6-3. or 12-6-7. )
Reconnect the connector of thermistor.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more
without showing thermistor abnormality?
OK.
(Cause is poor contact.)
Yes
Yes
g Check of outdoor thermistors
Disconnect the connector of thermistor in the outdoor P.C. board (see
below table), and measure the resistance of thermistor.
Connect the compressor and activate the inverter. Then measure the
time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit.
(TEST RUN OPERATION : Refer to page 31 for SLZ/SUZ and
page 37 SEZ/SUZ.)
<<Measurement>>
Measure the time from the start of compressor to the stop of
compressor due to overcurrent.