88
a How to check inverter/compressor
Are the voltages balanced?
Disconnect the connector (CN61) between
compressor and the intelligent power module
(IPM).
Replace the inverter P.C. board.
Check the voltage between terminals.
Check the compressor.
See
d
“Check of compressor”.
No
Yes
See
b
“Check of open phase”.
With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if
the inverter is normal by measuring the balance of voltage between the terminals.
The output voltage values have the tolerance of ± 20%.
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION
: Refer to page 31 for SLZ/SUZ and page 37 for SEZ/SUZ.)
<<Measurement point>>
At 3 points
BLK (U) - WHT (V)
BLK (U) - RED (W)
WHT (V) - RED (W)
NOTE
: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 12-6-3. (KA25/35VA) or 12-6-7.)
Refer to
f
“Check of compressor operation
time”.
Does the compressor operate continuously?
Check the refrigerant circuit.
OK.
No
Yes
Refer to
e
“Check of compressor winding”.
Is the compressor normal?
Replace the compressor.
No
Yes
d Check of compressor
b Check of open phase
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
9-time flash
2.5-second OFF
Is the compressor
operation time more than
10 seconds?
No
Replace the compressor.
Yes